| Plan Review Notes For Permit 05020246 |
| Permit Number |
05020246 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT L-3 SHOW THE LOCATION OF THE | | | CONTROLLER/TIMER, AND RAIN SENSOR. | | | SECTION 104.2.1. | | | 2) SGT C.5 RPZ BACKFLOW IS REQUIRED ON | | | THE WATER SERVICE TO EACH BUILDING. | | | SECTION 608.13.2. | | | 3) INDICATE THE SF AREA FOR EACH UNIT TO | | | CALCULATED THE MINIMUM FACILITIES PER | | | TABLES 1003.1 & 403.1. | | | 4) SHT A301 SHOW THE SQUARE FOOTAGE FOR | | | ALL SPACES INCLUDING MEZZNINE LEVEL. | | | SHOW SF FOR EACH OCCUPANCY. (OFFICE AND | | | STORAGE). SECTION 104.2.1. | | | 5) SHT A3.06 DETAIL #8 PROVIDE | | | CALCULATIONS SHOWING COMPLIANCE WITH | | | SECTIONS 11-4.26.3(2)(3)(4). | | | CALCULATIONS FROM THE ENGINEER REQD. | | | 6) SHT A3.06 SHOW COMPLIANCE WITH | | | SECTION 11-4.19.4 EXPOSED PIPES & | | | SURFACES. | | | 7) SHTS P5.01 & P5.02 WATER RISER | | | DIAGRAMS, SECTION 606.1(4) FULL OPEN | | | VALVES ARE REQUIRED ON EVERY WATER DOWN | | | FEED PIPE. SECTION 606.2(2) SHUT OFF | | | VALVES REQUIRED FOR HOSE BIBBS. SHOW | | | THESE VALVES ON THE ISOMETRIC. SECTION | | | 104.3.1.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|