Plan Review Notes
Plan Review Notes For Permit 05020246
Permit Number 05020246
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT L-3 SHOW THE LOCATION OF THE
 CONTROLLER/TIMER, AND RAIN SENSOR.
 SECTION 104.2.1.
 2) SGT C.5 RPZ BACKFLOW IS REQUIRED ON
 THE WATER SERVICE TO EACH BUILDING.
 SECTION 608.13.2.
 3) INDICATE THE SF AREA FOR EACH UNIT TO
 CALCULATED THE MINIMUM FACILITIES PER
 TABLES 1003.1 & 403.1.
 4) SHT A301 SHOW THE SQUARE FOOTAGE FOR
 ALL SPACES INCLUDING MEZZNINE LEVEL.
 SHOW SF FOR EACH OCCUPANCY. (OFFICE AND
 STORAGE). SECTION 104.2.1.
 5) SHT A3.06 DETAIL #8 PROVIDE
 CALCULATIONS SHOWING COMPLIANCE WITH
 SECTIONS 11-4.26.3(2)(3)(4).
 CALCULATIONS FROM THE ENGINEER REQD.
 6) SHT A3.06 SHOW COMPLIANCE WITH
 SECTION 11-4.19.4 EXPOSED PIPES &
 SURFACES.
 7) SHTS P5.01 & P5.02 WATER RISER
 DIAGRAMS, SECTION 606.1(4) FULL OPEN
 VALVES ARE REQUIRED ON EVERY WATER DOWN
 FEED PIPE. SECTION 606.2(2) SHUT OFF
 VALVES REQUIRED FOR HOSE BIBBS. SHOW
 THESE VALVES ON THE ISOMETRIC. SECTION
 104.3.1.1.
  
 REVIEW BY KEN STEVENS