| Plan Review Notes For Permit 05020246 |
| Permit Number |
05020246 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-21 00:00:00 | DENIED: | | | 1.PLAN SHEET M8.01 DETAIL 2, THE | | | DETAIL FOR THE AHU INDICATES AN OVERFLOW | | | SWITCH IN THE UNIT DRAIN PAN.PER 2001 | | | FBC/M 307.2.3, AN AUXILIARY DRAIN PAN IS | | | REQUIRED WITH THE FLOAT SWITCH INSTALLED | | | IN THE AUXILIARY DRAIN PAN.THE CODE | | | DOES NOT ALLOW FOR THE INSTALLATION AS | | | DEPICTED IN DETAIL 2. | | | | | | 2.PLEASE INDICATE AT WHAT HEIGHT THE | | | AHU WILL BE INSTALLED. | | | | | | 3.PLEASE NOTE, SYSTEMS WIHT THE DESIGN | | | CAPACITY GREATER THAN 2,000 CFM ARE | | | REQUIRED TO BE EQUIPPED WITH A DUCT | | | SMOKE DETECTOR.PLEASE REFERENCE AC-3 | | | ON THE EQUIPMENT SCHEDULE. | | | | | | PLANS ARE OTHERWISE CODE COMPLIANT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. | | | | | | |
|