Plan Review Notes
Plan Review Notes For Permit 05020246
Permit Number 05020246
Review Stop M
Sequence Number 1
Notes
Date Text
2005-03-21 00:00:00DENIED:
 1.PLAN SHEET M8.01 DETAIL 2, THE
 DETAIL FOR THE AHU INDICATES AN OVERFLOW
 SWITCH IN THE UNIT DRAIN PAN.PER 2001
 FBC/M 307.2.3, AN AUXILIARY DRAIN PAN IS
 REQUIRED WITH THE FLOAT SWITCH INSTALLED
 IN THE AUXILIARY DRAIN PAN.THE CODE
 DOES NOT ALLOW FOR THE INSTALLATION AS
 DEPICTED IN DETAIL 2.
  
 2.PLEASE INDICATE AT WHAT HEIGHT THE
 AHU WILL BE INSTALLED.
  
 3.PLEASE NOTE, SYSTEMS WIHT THE DESIGN
 CAPACITY GREATER THAN 2,000 CFM ARE
 REQUIRED TO BE EQUIPPED WITH A DUCT
 SMOKE DETECTOR.PLEASE REFERENCE AC-3
 ON THE EQUIPMENT SCHEDULE.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  