| Plan Review Notes For Permit 05020246 |
| Permit Number |
05020246 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-22 00:00:00 | 1) PLEASE BE ADVISED THAT ALL LIFE | | | SAFETY MUST COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 2) THE TURN AROUND LOCATED NEXT TO THE | | | 10' UTILITY EASEMENT MUST PROVIDE A | | | CENTERLINE TURNING RADIUS OF 50'. | | | | | | 3) PLEASE BE ADVISED THAT THE FIRE | | | DEPARTMENT CONNECTION SHALL BE LOCATED | | | NO FURTHER THAN 150' FROM THE CLOSEST | | | FIRE HYDRANT. | | | | | | 4) PLANS DON'T REFLECT ANY FIRE HYDRANTS | | | ON THE WEST SIDE OF THE PROJECT. ARE | | | THERE ANY, AND COULD YOU PROVIDE THE | | | LOCATIONS? | | | | | | 5) WILL THERE BE GATE ACCESS INTO THE | | | PROPERTY AFTER HOURS? IF SO, PLEASE BE | | | ADVISED THAT A KNOX KEY SYSTEM SHALL BE | | | PROVIDED WITH A BACK UP IN THE EVENT OF | | | POWER FAILURE. | | | | | | | | | MIKE WENNERGREN, ACTING CAPTAIN | | | WPBFR(561) 835-2910 |
|