Plan Review Notes
Plan Review Notes For Permit 05020246
Permit Number 05020246
Review Stop B
Sequence Number 1
Notes
Date Text
2005-02-17 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05020246
 ADD: 5405 N HAVERHILL RD PH#2
 CONT:NORTON
 TEL: (561)252-0590
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 1)PROVIDE NOC RECORDED WITH THE CLERK OF
 COURT BEFORE A PERMIT CAN BE
 ISSUED.A0.01 CORRECT NOTE THAT NOC WILL
 BE REQUIRED BY FIRST INSPECTION,
 BUILDING OFFICIAL IS MORE RESTRICTIVE.
  
 2) SINCE THE IST REVIEW OF PHASE #1, A
 REPLAT WAS SUBMITTED, THIS LOT CAN NO
 LONGER USE THIS ADDRESS , EACH PCN HAS
 ITS OWN ADDRESS, IT WILL BE ASSIGNED
 WITH THE NEW PCN.
  
 3) E2.02/E2.03 WHEN THE SPACE BENEATH
 MEZZANINES ARE ENCLOSED MUST COMPLY WITH
 1005.7.3 (EXCEPTION) A SMOKE DETECTION
 SYSTEM SHALL BE PLACED BENEATH A
 ENCLOSED MEZZANINE WHICH SOUNDS A ALARM
 IN THE MEZZANINEIN ACCORDANCE WITH
 NFPA 72.
  
 4) FBC* 105.3RESIDENT INSPECTOR.
 SUBMIT INSPECTOR RESUME' AND LICENSE
 DOCUMENTS TO HAROLD PISKURA, DIRECTOR OF
 THE RESIDENT INSPECTOR PROGRAM.A
 RESIDENT INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF
 THE FOLLOWING:
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 XX - BUILDING/STRUCTURES OF UNUSUAL
 DESIGN OR METHODS OF CONSTRUCTION
 (TILT WALL CONSTRUCTION)
  
 5)106.4.2 STORAGE & FACTORY- INDUS-
 TRIAL OCCUPANCIES. IT SHALL BE THE
 RESPONSIBILITY OF THE OWNER, AGENT,
 PROPIETOR OR OCCUPANT OF GROUP S AND
 GROUP F OCCUPANCIES, OR ANY OCCUPANCY
 WHERE EXCESSIVE FLOOR LOADING IS LIKELY
 TO OCCUR, TO EMPLOY A COMPETENT ARCHI-
 TECT OR ENGINEER IN COMPUTING THE SAFE
 FLOOR LOAD CAPACITY. ALL SUCH COMPUTA-
 TIONS SHALL BE ACCOMPANIED BY AN AFFA-
 DAVIT FROM THE ARCHITECT OR ENGINEER
 STATING THE SAFE ALLOWABLE FLOOR LOADS
 ON EACH FLOOR IN POUNDS PER SQ FT.THE
 COMPUTATIONS & AFFADAVIT SHALL BE FILED
 AS A PERMANENT RECORD OF THE BLDG DEPT.
  
 6) THESE ARE CODE REQUIREMENTS FOR
 TERMITE PROTECTION NOT FOUND IN 1816:
 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS FIXED & STOREFRONT: REPORTS
 WERE SRUNK & COPIED UNREADABLE,
 FASTEN REPORTS TOGETHER MISSING
 STOREFRONT. THREE COPIES.
 B) EXTERIOR SWING DOORS-3 COPIES
 C) GARAGE DOORS- PARTIAL REPORT, 3
 COPIES
 D) MULLIONS- NO SUBMITTALS
 E) STORM SHUTTERS- NO SUBMITTAL, 3
 COPIES
 F) ROOFING ASSEMBLIES- 3 COPIES
  
 8A)!!!!!!!!PLEASE TAKE NOTE!!!!!!!!!!!!
 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE
 REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8B) NOT A CODE ISSUE, BUT REFRENCED IN
 THE PLANS THE ARCHITECT OF RECORD IS TO
 REVIEW AND APPROVE ALL COMPONENTS &
 CLADDING.
  
 8C) THE PRODUCT APPROVALS FOR PGT FIXED
 WINDOWS (2) REPORTS WERE SUBMITTED, ONE
 FOR LARGE MISSLE IMPACT OR GLAZING NOT
 RATED, INDICATE WHICH IS TO BE USED.
 THEN A SECOND REPORT WAS SUBMITTED FOR
 F6000, EACH REPORT HAS DIFFERENT
 PRESSURES WHICH REPORT IS TO BE USED?
  
 9A)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 DISCREPANCY SEE A9.02 SEE WINDOW
 SCHEDULE AND NOTE #1, EITHER IMPACT
 WINDOWS ARE TO BE USED OR STORM
 SHUTTERS.
  
 9B) PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH
 SPECIFIC ANCHORS AND MOUNTING TO BE USED
 FOR ALL NON-IMPACT GLAZING.COMMERCIAL
 AREA WHERE SHUTTERS WILL BE STORED.
 FBC 1606.1.4.
  
 9C)FL BLD CODE 2001 SECTION 103.6,
 1606.1.4, 1707.4 & 3401.7.2.4.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION
 SCHEDULE SUMMARIZING & IDENTIFYING
 OPENING SIZES, STORY HEIGHTS, UNIT MARK
 NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM
 BAR REINFORCING REQUIREMENTS, WALL PRES-
 SURE ZONES, SLAT TYPES, ETC., SHALL BE
 SUBMITTED AT TIME OF PERMIT APPLICATION
 TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
  
 9D) SEE A9.02 PLANS INDICATE THE USE OF
 STORM SHUTTERS, SEE CITY INTERPRETATION
 ON THE STANDARD FOR HURRICANE MISSLE
 IMPACT PROTECTION, QUESTION #13, DEALING
 WITH THE "PRESTORM HURRICANE PREPARDNESS
 PLAN" SUBMIT FOR REVIEW. SEE ATTACHMENT.
  
 10) A0.01 CONTRACTOR PRICING
 REQUIREMENTS FBC SECTION 104.6.4.5, NOT
 FOUND IN THE ADMINISTRATIVE CODE NOR THE
 CITY ADOPTED ADMINISTRATIVE CODE?
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved