| Plan Review Notes For Permit 05020237 |
| Permit Number |
05020237 |
|
| Review Stop |
E |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2006-06-25 00:00:00 | *** PLEASE SEE RISER SHOW PANEL "C" AS | | | 100A AND PANEL "C" SCHEDULE SHOWS 125A. | | | | | | PLEASE CORRELATE BEFORE FINAL. | | | THIS CAN BE ADDRESSED IN LTR FORM AS | | | LONG AS THERE ARE NO OTHER | | | REVISIONS/CHANGES. | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICALPLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|