Plan Review Notes
Plan Review Notes For Permit 05020237
Permit Number 05020237
Review Stop E
Sequence Number 7
Notes
Date Text
2006-06-09 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE IN NO CASE CAN WHITE
 OUT BE USED ON PLANS WHICH ARE SIGNED,
 DATED AND SEALED. FS 471/481
 PLEASE SEE CONDUCTORS ON PLANS CHANGED
 FROM 3/0'S TO 2/0'S FROM ALL PREVIOUS
 DESIGNS ON PLANS.
 215.5
  
 2) NOTE: PLEASE CORRELATE RISER WITH
 FEEDERS SHOWN ON PANEL "B" FOR PANEL
 "C".
 PLEASE SEE TWO DIFFERENT SIZES ARE
 SHOWN?
 215.5
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]