Plan Review Notes
Plan Review Notes For Permit 05020237
Permit Number 05020237
Review Stop E
Sequence Number 5
Notes
Date Text
2006-03-18 00:00:00********* UNSAT *********
  
 PLEASE SEE SOME COMMENTS FROM PREVIOUS
 REVIEW AND SOME NEW COMMENTS DUE TO
 CHANGES IN PLANS.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW WIHT NEW
 NOTES ADDED.
  
  
 1)NOTE: NOTE #1 NO, SPOKE TO CONTRACTOR,
 HE WILL COME IN AND ADJUST.
  
 ** PREVIOUS NOTE**
 PLEASE SEE THERE HAVE BEEN MAJOR
 CHANGES IN THE SCOPE OF ELECTRICAL WORK
 AND OTHER REMODEL WORK DONE FOR
 DWELLING.
 PLEASE SEE FBC ADMINSTRATIVE 104.6.5
 WHICH REQUIRES A MAJOR ADJUSTMENT IN
 VALUATION OF PERMITTING.
 PLEASE SEE ORIG WAS INCLUSIVE OF SOME
 REMODEL AND ADDITION WORK AT $130,000
 PLEASE ADJUST.
 PLANS ARE NOW INDICATING THE ENTIRE
 HOUSE BEING REWIRED ETC.
  
 2)NOTE: NOTE #2 NO, PLEASE SEE REDLINED
 PLANS. THESE LOCATIONS COULD BE
 REDLINED, HOWEVER PLANS ARE COMING BACK
 FOR OTHER COMMENTS.
  
 ** PREVIOUS NOTE**
 PLEASE SEE SOME RECEPTS NOW
 MISSING DUE TO SOME WALL CHANGES.210.52
  
 3)NOTE: NOTE #3 OK? SPACE IN KITCHEN
 SEEMS TO BE 12" OR MORE, THIS IS TO BE
 FEILD VERIFIED AND IF ONE IS NEEDED, IT
 IS TO BE ADDED.
  
 ** PREVIOUS NOTE **
 PLEASE BE SURE TO DOUBLE CHECK
 KITCHEN COUNTERSPACE AS SOME SPACING
 SEEMS TO REQUIRE ADDITIONAL
 RECEPTS.210.52C1
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE NEW
 COMMENTS DUE TO CHANGES NOW MADE AND
 SOME ITEMS ARE MISSING.
  
 ** PREVIOUS NOTE**
 PLEASE SEE COMPLETE CHANGE IN
 ELECTRICAL SERVICE HAS NOW CREATED SOME
 ELECTRICAL COMMENTS:
  
 A)OK
  
 B)OK
  
 C)OK, HOWEVER SEE CONDUITS FROM MAINS AT
 HOUSE TO SUB PANELS AT HOUSE ARE MISSING
 EQUIPMENT GROUNDING CONDUCTOR.
 250.110,250.122
 ** PRE-NOTE**
 PLEASE SEE MISSING EQUIPMENT GROUNDING
 CONDUCTORS FROM METER/MAIN UP TO MAIN
 HOUSE. 250.32
 PLEASE ALSO SEE MISSING GROUNDING
 ELECTRODE SYSTEM AT MAIN HOUSE, SINCE
 SERVICE IS NOW MOVED.
  
 D) OK, PLEASE SEE OCP WAS ADDED ,
 HOWEVER SEE NEW NOTE AS 100A OCP IN
 METERMAIN IS FEEDING A 70 BRKR PANEL.
 PLEASE VERIFY AS EITHER THE GUEST HOUSE
 BRKR PANEL IS 100A'S, OR BRKR AT METER
 MAIN IS 70A'S?
  
 ** PRE-NOTE**PLEASE SEE METER/MAIN IS
 SHOWN AS
 400A, AND THERE IS NO INDICATION OF THE
 OCP PROVIDED FOR SUB-PANEL FEEDERS TO
 MAIN HOUSE OR ANY OTHER BRANCH BRKRS.
 240.4,310.16 ETC.
 PLEASE ALSO VERIFY GUEST HOUSE BEING
 SHOWN WITH A MAIN DISCONNECT AND
 SUB-PANEL, AS IT IS SHOWN ON RISER BEING
 FED FROM THE METER MAIN PANEL AT GUEST
 HOUSE BLDG ALREADY?
 DISC?
  
 E) NO, PLEASE SEE PANEL SCHEDULES STILL
 SHOW PANEL AS 200A MCB WHICH IS OK,
 HOWEVER PLEASE SEE RISER DIAGRAM NOW
 SHOWS THE PANELS LOCATED INSIDE AS MLO??
 PLEASE CORRELATE.
  
 ** PRE-NOTE**
 PLEASE ALSO VERIFY THE PANELS INSIDE
 THE MAIN HOUSE AS BOTH ARE SHOWN WITH
 MCB'S WHICH ARE PERMITTED ALTHOUGH NOT
 REQUIRED. THIS IS ONLY A NOTE AND NO
 CHNAGE IS NEEDED. PLEASE KNOW, IF SHOWN
 AS MCB , THEN THESE WILL BE REQUIRED.
  
 F) OK.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 OK.
  
 9)NOTE: NOTE # 9 OK.
  
 10)NOTE: NOTE #10 OK , NOTED.
  
 ** NOW NOTE**
  
 11)NOTE: PLEASE CORRELATE LOADS SHOWN
 ON PANEL "C" AND LOAD ON PANEL "B" FOR
 PANEL "C" LOAD. PREVIOUS PLANS, THESE
 MATCHED, BUT HAVE NOW BEEN CHANGED.
  
 12)NOTE: PLEASE KNOW, RISER SHOWS "IRON"
 GROUND RODS, THIS IS OK, HOWEVER DOES
 NOT SEEM TO BE A COMMON GE. THIS SI ONLY
 A NOTE:
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  