| Date |
Text |
| 2006-03-18 00:00:00 | ********* UNSAT ********* |
| | |
| | PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| | REVIEW AND SOME NEW COMMENTS DUE TO |
| | CHANGES IN PLANS. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW WIHT NEW |
| | NOTES ADDED. |
| | |
| | |
| | 1)NOTE: NOTE #1 NO, SPOKE TO CONTRACTOR, |
| | HE WILL COME IN AND ADJUST. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE THERE HAVE BEEN MAJOR |
| | CHANGES IN THE SCOPE OF ELECTRICAL WORK |
| | AND OTHER REMODEL WORK DONE FOR |
| | DWELLING. |
| | PLEASE SEE FBC ADMINSTRATIVE 104.6.5 |
| | WHICH REQUIRES A MAJOR ADJUSTMENT IN |
| | VALUATION OF PERMITTING. |
| | PLEASE SEE ORIG WAS INCLUSIVE OF SOME |
| | REMODEL AND ADDITION WORK AT $130,000 |
| | PLEASE ADJUST. |
| | PLANS ARE NOW INDICATING THE ENTIRE |
| | HOUSE BEING REWIRED ETC. |
| | |
| | 2)NOTE: NOTE #2 NO, PLEASE SEE REDLINED |
| | PLANS. THESE LOCATIONS COULD BE |
| | REDLINED, HOWEVER PLANS ARE COMING BACK |
| | FOR OTHER COMMENTS. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE SOME RECEPTS NOW |
| | MISSING DUE TO SOME WALL CHANGES.210.52 |
| | |
| | 3)NOTE: NOTE #3 OK? SPACE IN KITCHEN |
| | SEEMS TO BE 12" OR MORE, THIS IS TO BE |
| | FEILD VERIFIED AND IF ONE IS NEEDED, IT |
| | IS TO BE ADDED. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE BE SURE TO DOUBLE CHECK |
| | KITCHEN COUNTERSPACE AS SOME SPACING |
| | SEEMS TO REQUIRE ADDITIONAL |
| | RECEPTS.210.52C1 |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 OK. |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE NEW |
| | COMMENTS DUE TO CHANGES NOW MADE AND |
| | SOME ITEMS ARE MISSING. |
| | |
| | ** PREVIOUS NOTE** |
| | PLEASE SEE COMPLETE CHANGE IN |
| | ELECTRICAL SERVICE HAS NOW CREATED SOME |
| | ELECTRICAL COMMENTS: |
| | |
| | A)OK |
| | |
| | B)OK |
| | |
| | C)OK, HOWEVER SEE CONDUITS FROM MAINS AT |
| | HOUSE TO SUB PANELS AT HOUSE ARE MISSING |
| | EQUIPMENT GROUNDING CONDUCTOR. |
| | 250.110,250.122 |
| | ** PRE-NOTE** |
| | PLEASE SEE MISSING EQUIPMENT GROUNDING |
| | CONDUCTORS FROM METER/MAIN UP TO MAIN |
| | HOUSE. 250.32 |
| | PLEASE ALSO SEE MISSING GROUNDING |
| | ELECTRODE SYSTEM AT MAIN HOUSE, SINCE |
| | SERVICE IS NOW MOVED. |
| | |
| | D) OK, PLEASE SEE OCP WAS ADDED , |
| | HOWEVER SEE NEW NOTE AS 100A OCP IN |
| | METERMAIN IS FEEDING A 70 BRKR PANEL. |
| | PLEASE VERIFY AS EITHER THE GUEST HOUSE |
| | BRKR PANEL IS 100A'S, OR BRKR AT METER |
| | MAIN IS 70A'S? |
| | |
| | ** PRE-NOTE**PLEASE SEE METER/MAIN IS |
| | SHOWN AS |
| | 400A, AND THERE IS NO INDICATION OF THE |
| | OCP PROVIDED FOR SUB-PANEL FEEDERS TO |
| | MAIN HOUSE OR ANY OTHER BRANCH BRKRS. |
| | 240.4,310.16 ETC. |
| | PLEASE ALSO VERIFY GUEST HOUSE BEING |
| | SHOWN WITH A MAIN DISCONNECT AND |
| | SUB-PANEL, AS IT IS SHOWN ON RISER BEING |
| | FED FROM THE METER MAIN PANEL AT GUEST |
| | HOUSE BLDG ALREADY? |
| | DISC? |
| | |
| | E) NO, PLEASE SEE PANEL SCHEDULES STILL |
| | SHOW PANEL AS 200A MCB WHICH IS OK, |
| | HOWEVER PLEASE SEE RISER DIAGRAM NOW |
| | SHOWS THE PANELS LOCATED INSIDE AS MLO?? |
| | PLEASE CORRELATE. |
| | |
| | ** PRE-NOTE** |
| | PLEASE ALSO VERIFY THE PANELS INSIDE |
| | THE MAIN HOUSE AS BOTH ARE SHOWN WITH |
| | MCB'S WHICH ARE PERMITTED ALTHOUGH NOT |
| | REQUIRED. THIS IS ONLY A NOTE AND NO |
| | CHNAGE IS NEEDED. PLEASE KNOW, IF SHOWN |
| | AS MCB , THEN THESE WILL BE REQUIRED. |
| | |
| | F) OK. |
| | |
| | 7)NOTE: NOTE #7 OK |
| | |
| | 8)NOTE: NOTE #8 OK. |
| | |
| | 9)NOTE: NOTE # 9 OK. |
| | |
| | 10)NOTE: NOTE #10 OK , NOTED. |
| | |
| | ** NOW NOTE** |
| | |
| | 11)NOTE: PLEASE CORRELATE LOADS SHOWN |
| | ON PANEL "C" AND LOAD ON PANEL "B" FOR |
| | PANEL "C" LOAD. PREVIOUS PLANS, THESE |
| | MATCHED, BUT HAVE NOW BEEN CHANGED. |
| | |
| | 12)NOTE: PLEASE KNOW, RISER SHOWS "IRON" |
| | GROUND RODS, THIS IS OK, HOWEVER DOES |
| | NOT SEEM TO BE A COMMON GE. THIS SI ONLY |
| | A NOTE: |
| | 215.5 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |