| 2005-03-25 00:00:00 | ******* UNSAT 2ND REVIEW ********** |
| | |
| | PLEASE SEE SOME ITEMS FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | |
| | 1)NOTE: NOTE #1 OK. |
| | |
| | 2)NOTE: NOTE #2 NO, PLEASE SEE MISSING |
| | ONE. |
| | |
| | 3)NOTE: NOTE #3 OK |
| | |
| | |
| | 4)NOTE: NOTE #4 OK, HOWEVER PLEASE SEE |
| | TWO SD'S WHICH APPEAR TO HAVE BEEN ADDED |
| | TODINING RM? |
| | THIS IS ONLY A NOTE AND ARE PERMITTED, |
| | IF SHOWN ON PLANS THEN THEY MUST BE |
| | INSTALLED. |
| | |
| | 5)NOTE: NOTE #5 OK |
| | |
| | 6)NOTE: OK, HOWEVER PLEASE CLARIFY HOW |
| | DETACHED BLDG IS BEING FED? |
| | 225.31,250.32 ETC. |
| | |
| | 7)NOTE: NOTE #7 OK |
| | |
| | 8)NOTE: NOTE #8 OK, HOWEVER NOW THAT |
| | PANEL SCHEDULES HAVE BEEN SUBMITTED FOR |
| | REVIEW WITH CIRCUITING/OCP ETC, PLEASE |
| | SEE NEW COMMENTS AT END OF THIS REVIEW. |
| | |
| | 9)NOTE: NOTE #9 OK |
| | |
| | 10)NOTE; NOTE #10 OK |
| | |
| | 11)NOTE: NOTE #11 NO, PLEASE SEE TWO |
| | LOCATIONS REDLINED ON PLANS ON SECOND |
| | FLR. |
| | |
| | 12)NOTE: NOTE # 12 OK |
| | |
| | 13)NOTE: NOTE #13 OK |
| | |
| | 14)NOTE: NOTE #14 NO, PLEASE SEE BOTH |
| | AHU'S STILL DO NOT SHOW DISC'S. PLEASE |
| | SEE PLANS REDLINED. |
| | |
| | 15)NOTE: NOTE #15 OK. |
| | |
| | 16)NOTE: NOTE #16, NO, SAME NOTE. 5' |
| | STILL INDICATED. |
| | |
| | NEW NOTES. |
| | |
| | 1)NOTE: PLEASE SEE END OF NOTES ON |
| | PREVIOUS REVIEW. |
| | PLEASE REMOVE ALL OLD/VOIDED SHEETS IN |
| | SETS AND INSERT ONLY NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. |
| | PLEASE SEE THIS IS TO HELP IN THE |
| | PROCESS AND EXPEDITE PLANS. PLAN SETS |
| | SHALL BE COMPLETE SETS WHEN SUBMITTING. |
| | ONE SET OF OLD SHEETS SHOULD BE |
| | SUBMITTED SEPARATELY FOR REFERENCE ONLY. |
| | |
| | 2)NOTE: PLEASE SEE 424.3B FORMIN OCP |
| | FOR AHU'S. PLEASE SEE PLANS REDLINED. |
| | |
| | 3)NOTE: PLEASE CORRELATE PANEL "B" WITH |
| | RISER DIAGRAM FOR POOL SUB PANEL. |
| | ONE SHOWS 1/0'S AND THE OTHER #1'S. |
| | |
| | 4)NOTE: PLEASE SEE RANGE/OVEN SHOWN AS |
| | 2P30A W/# 10AWG, YET RANGE IS SHOWN AS |
| | MIN 8KW ON LOAD CALCULATIONS. |
| | PLEASE VERIFY SIZE OF RANGE/OVEN AND |
| | PROVIDE MIN OCP/AWG. |
| | |
| | 5)NOTE: PLEASE SEE PLANS AND PANEL |
| | SCHEDULES BOTH INDICATE WATER HEATERS ON |
| | BOTH LEVELS, HOWEVER LOAD CALCULATIONS |
| | ONLY INDICATE ONE WATER HEATER?? |
| | PLEASECORRELATE. |
| | |
| | 6)NOTE: PLEASE CORRELATE APPLIANCE LOADS |
| | ON LOAD CALCULATIONS AS SHOWN ON PANEL |
| | SCHEDULE. |
| | PLEASE SEE PANEL SCHEDULES INDICATE SM |
| | APPL AS 360VA AND 1500 VA. |
| | PLEASE SEE A MIN OF 1500 VA IS REQUIRED |
| | FOR "EACH" SMALL APPL CIRCUIT PROVIDED. |
| | PLEASE ADJUST PANEL SCHEDULE AND LOAD |
| | CALCS. |
| | |
| | 7)NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES WASHER AS 360 VA ALSO, YET |
| | LOAD CALCS INDICATE 1500 VA AS REQUIRED |
| | UNDER 220.16, 220.11, 210.52 |
| | |
| | 8)NOTE: PLEASE SEE WHIRLPOOL TUB SHOWN |
| | ON LOAD CALCUALTIONS, YET NOT ON PANEL |
| | SCHEDULES? |
| | |
| | 9)NOTE: PLEASE SEE MISSING FRONT GFI |
| | RECEPT AS REQUIRED PER 210.52E , NOT A |
| | COMMENT ON FIRST REVIEW. |
| | |
| | 10)NOTE: PLEASE SEE ATTACHED COPY OF FS |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONAL. |
| | THIS IS A NOTICE ONLY GIVEN AT THIS |
| | TIME. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |