| 2005-02-14 00:00:00 | ******** UNSAT********* |
| | |
| | 1)NOTE: PLEASE SEE 210.52C1 FOR REQUIRED |
| | RECETPS ALONG KITCHEN COUNTERSPACE. |
| | |
| | 2)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS |
| | SERVING KITCHEN COUNTERSPACE ARE TO BE |
| | GFI/GFI PROTECTED. |
| | |
| | 3)NOTE: PLEASE SEE MISSING GFI FOR UPPER |
| | BATH RM. 210.52D/210.11C3 |
| | |
| | 4)NOTE:SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | PLEASE SEE PLANS HAVE BEEN REDLINED FOR |
| | MIN LOCATIONS. |
| | |
| | 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 6)NOTE: PLEASE SEE RISER SHOWS ONE METER |
| | , YET PLANS INDICATES TWO? PLEASE |
| | CORRELATE AND SEE ZONING FOR ANY |
| | POSSIBLE COMMENTS FOR MORE THAN ONE |
| | METER. |
| | |
| | 7)NOTE: PLEASE SEE 250.6,250.24, |
| | EQUIPMNET GROUNDING CONDUCTORS ARE |
| | INSTALLED AFTER THE FIRST MEANS OF DISC. |
| | |
| | 8)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S) |
| | SHOWING MIN CIRCUITS REQUIRED ALONG WITH |
| | OCP AND AWG. |
| | 215.5 |
| | |
| | 9) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. PER 210.52D, 210.11C3 |
| | |
| | 10)NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 11)NOTE: PLEASE SEE 210.52 FOR SOME |
| | RECEPTS MISSING IN RMS WHICH ARE BEING |
| | REMODELED. |
| | |
| | 12)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 13)NOTE: PLEASE VERIFY LOCATION OF POOL |
| | PANEL, APPEARS TO BE SHOWN "IN" |
| | WALL/COLUMN? |
| | PLEASE SEE 110.26 FOR MIN CLEARENCE. |
| | |
| | 14)NOTE: PLEASE SHOW ALL DISC'S REQUIRED |
| | FOR A/C EQUIPMENT SHOWN. 440.11 |
| | |
| | 15)NOTE: PLEASE SEE MISSING GFI FOR A/C |
| | EQUIPMENT. 210.63 |
| | |
| | 16)NOTE: PLEASE SEE "NOTE#6" OF |
| | ELECTRICAL NOTES. MENTIONS ALL RECEPT |
| | W/IN 5FT, TO BE GFI. PLEASE SEE THIS |
| | MEASUREMENT SHOULD READ 6' , HOWEVER THE |
| | "93" NEC CHANGED TO REQUIRE ALL RECEPTS |
| | SERVING KITCHEN COUNTERSPACE TO BE |
| | GFI/GFI PROTECTED. PLEASE SEE PREVIOUS |
| | NOTE; |
| | |
| | PLEASE SEE MANY OF THE ABOVE ITEMS HAVE |
| | BEEN REDLINED ON ONE SET OF PLANS FOR |
| | AREAS OF COMMENTS. |
| | |
| | PLEASE REMOVE ANY/ OLD/VOIDED SHEETS AND |
| | ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING ME. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | ** ADDED NOTE: PLEASE PROVIDE ROOM |
| | DESIGNATIONS ON ELECTRICAL PLANS. |