2005-02-14 00:00:00******** UNSAT*********
  
 1)NOTE: PLEASE SEE 210.52C1 FOR REQUIRED
 RECETPS ALONG KITCHEN COUNTERSPACE.
  
 2)NOTE: PLEASE SEE 210.8A6, ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
  
 3)NOTE: PLEASE SEE MISSING GFI FOR UPPER
 BATH RM. 210.52D/210.11C3
  
 4)NOTE:SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE PLANS HAVE BEEN REDLINED FOR
 MIN LOCATIONS.
  
 5)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 6)NOTE: PLEASE SEE RISER SHOWS ONE METER
 , YET PLANS INDICATES TWO? PLEASE
 CORRELATE AND SEE ZONING FOR ANY
 POSSIBLE COMMENTS FOR MORE THAN ONE
 METER.
  
 7)NOTE: PLEASE SEE 250.6,250.24,
 EQUIPMNET GROUNDING CONDUCTORS ARE
 INSTALLED AFTER THE FIRST MEANS OF DISC.
  
 8)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S)
 SHOWING MIN CIRCUITS REQUIRED ALONG WITH
 OCP AND AWG.
 215.5
  
 9) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 10)NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 11)NOTE: PLEASE SEE 210.52 FOR SOME
 RECEPTS MISSING IN RMS WHICH ARE BEING
 REMODELED.
  
 12)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 13)NOTE: PLEASE VERIFY LOCATION OF POOL
 PANEL, APPEARS TO BE SHOWN "IN"
 WALL/COLUMN?
 PLEASE SEE 110.26 FOR MIN CLEARENCE.
  
 14)NOTE: PLEASE SHOW ALL DISC'S REQUIRED
 FOR A/C EQUIPMENT SHOWN. 440.11
  
 15)NOTE: PLEASE SEE MISSING GFI FOR A/C
 EQUIPMENT. 210.63
  
 16)NOTE: PLEASE SEE "NOTE#6" OF
 ELECTRICAL NOTES. MENTIONS ALL RECEPT
 W/IN 5FT, TO BE GFI. PLEASE SEE THIS
 MEASUREMENT SHOULD READ 6' , HOWEVER THE
 "93" NEC CHANGED TO REQUIRE ALL RECEPTS
 SERVING KITCHEN COUNTERSPACE TO BE
 GFI/GFI PROTECTED. PLEASE SEE PREVIOUS
 NOTE;
  
 PLEASE SEE MANY OF THE ABOVE ITEMS HAVE
 BEEN REDLINED ON ONE SET OF PLANS FOR
 AREAS OF COMMENTS.
  
 PLEASE REMOVE ANY/ OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING ME.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ** ADDED NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS ON ELECTRICAL PLANS.