| Notes |
| Date |
Text |
| 2005-03-29 00:00:00 | DENIED | | | | | | 1) THE TRUSS TIE DOWN SCHEDULE ON S4 | | | SPECIFIES A HDSA FOR MARK J. THERE IS NO | | | SUCH CONNECTOR IN THE SIMPSON CATALOG. | | | SHOULD THIS BE AN HD5A? ALSO INDICATE | | | HOW THE SPECIFIED ALLOWABLE UPLIFT OF | | | 8310 WAS DETERMINED. | | | | | | 2) THE MARK F CONNECTORS SPECIFIED FOR | | | THE MG1 TRUSSES DO NOT HAVE ADEQUATE | | | UPLIFT RESISTANCE. | | | | | | 3)DETAIL 10 ON S7 WHICH IS CALLED OUT ON | | | S4 FOR THE ROOF GIRDER TRUSSES INDICATES | | | THAT IT IS FOR FLOOR TRUSSES. PLEASE | | | CLARIFY. THE ARROW INDICATING THE | | | LOCATION IS NOT AT THE WALL AND DOES NOT | | | INDICATE THAT THIS CONNECTION IS FOR ALL | | | OF THE CENTER GIRDERS. | | | | | | 4) TWO OF THE ENERGY CALCS. DO NOT LIST | | | THE THE 2X6 EXTERIOR WOOD FRAME WALLS | | | AND INCORRECTLY SPECIFY R 19 INSULATION | | | IN THE CEILING. | | | | | | 5) SPECIFY ON THE PLANS THE MECHANICAL | | | CONNECTIONS FOR THE FL36 FLOOR TRUSSES | | | AT THE SECOND FLOOR STAIR OPENINGS AS | | | REQUIRED BY THE TRUSS DRAWINGS. THESE | | | FLOOR TRUSSES ARE NOT SHOWN ON THE | | | ARCHITECTURAL PLANS. | | | | | | 6) SUBMIT THE MIAMI-DADE NOA FOR THE | | | GLASS BLOCK. | | | | | | 7) SUBMIT THE MANUFACTURER'S SPECS. FOR | | | THE ROOF SHINGLES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|