| 2005-04-06 00:00:00 | DENIED |
| | |
| | 1) OWNER/AGENT IS REQUIRED TO SIGN THE |
| | ENERGY CALC FORMS. |
| | |
| | 2) THE ENERGY CALCS. DO NOT LIST THE 2X6 |
| | WOOD FRAME EXTERIOR WALLS. THE R-VALUE |
| | FOR THE CEILING INSULATION LISTED ON THE |
| | ENERGY CALC. FORMS DOES NOT MATCH THE |
| | PLANS. |
| | |
| | 3) THE HEADING FOR THE AREA TABULATION |
| | ON SHEET T-1 INCORRECTLY STATES 8 UNIT |
| | BUILDING. |
| | |
| | 4) SPECIFY THE MECHANICAL CONNECTORS FOR |
| | THE FL 36 FLOOR TRUSSES AND THE GF1 & |
| | GF2 ROOF TRUSSES. |
| | |
| | 5) THE ANCHOR SCHEDULE LISTS A SIMPSON |
| | HDSA CONNECTOR. IS THIS A TYPO FOR A |
| | HD5A CONNECTOR? HOW WAS THE MAXIMUM |
| | UPLIFT OF 8310# DETERMINED FOR THIS |
| | CONNECTOR. |
| | |
| | 6) THE UPLIFT IN THE TRUSS DRAWINGS |
| | EXCEEDS THE CAPACITY OF THE SPECIFIED |
| | CONNECTORS FOR THE MG1 TRUSSES. |
| | |
| | 7) SPECIFY THE CONNECTORS FOR EACH END |
| | OF THE GR2 TRUSSES AND THE CONNECTOR FOR |
| | THE GR3 AT THE INTERIOR WALL. |
| | |
| | 8) THE GR3 TRUSS IS INDICATED AS A TWO |
| | PLY TRUSS ON THE TRUSS DRAWINGS AND A |
| | FOUR PLY TRUSS ON S4 OF THE PLANS. |
| | |
| | 9) SUBMIT THE NOA (INSTALLATION |
| | INSTRUCTIONS) FOR THE ONE HOUR FIRE |
| | RATED GLASS BLOCK. |
| | |
| | 10) SUBMIT THE INSTALLATION INSTRUCTIONS |
| | FOR THE ASPHALT SHINGLES. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |