| Plan Review Notes For Permit 05020218 |
| Permit Number |
05020218 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-11 00:00:00 | | | | | | | PROVISO | | | ~~~~~~~ | | | | | | THE SMOKE DETECTORS ARE REQUIRED TO BE | | | INTERCONNECTED PER 905.2.1 FBC. CIRCUITS | | | #25 & 38 ARE USED ON PLAN. INSTALL PER | | | PANEL SCHEDULE. | | | | | | A RECEPTACLE MUST BE ADDED IN THE GUEST | | | BEDROOM PER 210.52(A)(1). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | | | | |
|