2005-08-06 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS TWO LISTS IN REGARDS
 TO SHOWING COMPLIANCE WITH FBC1005.4.
 THE FLOOR PLAN SHOWING WINDOW SIZES,
 ROOM LOCATIONS, TYPE OF WINDOWS IS NO
 LONGER IN THE PACKAGE.
  
 FROM PREVIOUS REVIEW, THE FOLLOWING
 COMMENTS.AS DISCUSSED WITH CONTRACTOR,
 I WILL PRINT THE PRODUCT APPROVALS
 REQUESTED IN WRITING FOR YOU.WHEN
 RESUBMITTING, PLEASE BE SURE THAT THIS
 REQUEST STAYS IN THE PACKAGE!
  
 2.)THE COVER SHEET TO A POMA SHUTTER
 NOA WAS SUBMITTED.PLEASE PROVIDE A
 COMPLETE, LEGIBLE TEST REPORT AND
 FLORIDA STATE OR LOCAL PRODUCT APPROVAL.
  
 3.)PROVIDE A FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL FOR THE WINDOW (NOA WAS
 PROVIDED), TWO COPIES.
  
 4.)TEST REPORT AND FLORIDA STATE OR
 LOCAL PRODUCT APPROVAL REQUIRED FOR THE
 MULLIONS.
  
 PRODUCT APPROVALS ARE AVAILABLE AT
 WWW.FLORIDABUILDING.ORG.
  
 5.)THE APPLICATION IS NO LONGER IN THE
 PACKAGE.
  
 6.)AS DISCUSSED, PLEASE COMPLETE THE
 ATTACHEDHURRICANE SHUTTER INSTALLATION
 SCHEDULE AS PER CITY POLICY.