Plan Review Notes
Plan Review Notes For Permit 05020193
Permit Number 05020193
Review Stop B
Sequence Number 1
Notes
Date Text
2005-02-09 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)FLOOR LEVELING IS ON THE PLAN,
 PLAN
 SPECIFIES SHUTTERS.NEITHER IS ON THE
 APPLICATION.PLEASE PROVIDE A
 REASONABLE VALUE FOR THE JOB (NOT THE
 VALUE OF YOUR SERVICES; VALUE IS TO
 INCLUDE MATERIALS AND LABOR AS A PERMIT
 WAS NOT APPLIED FOR PREVIOUSLY FOR THE
 WINDOWS).
  
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)AS PER CONVERSATION WITH
 CONTRACTOR, WINDOWS WERE INSTALLED
 (APPARENTLY WITHOUT A PERMIT) IMPROPERLY
 BY OTHERS.PLEASE PROVIDE TEST REPORTS
 AND FLORIDA OR LOCAL PRODUCT APPROVALS
 FOR THE FOLLOWING, AS PER THE PLAN:
 SINGLE HUNG WINDOWS
 MULLIONS
 IMPACT PROTECTION (UNLESS WINDOWS ARE
 IMPACT GLASS)
 FIXED WINDOW
  
 4.)PROVIDE A LEGIBLE SEAL,
 FAC61G1-15.
  
 5.)THE STRUCTURAL NOTES #13 AND BUCK
 DETAIL CONFLICT.PLEASE PROVIDE AN
 ATTACHMENT DETAIL OR SPEC WITH SPACING.
 (CAN'T HAVE 1 1/4" EMBEDMENT WITH A 2
 1/4" TAPCON ON A 2X4 BUCK.)
  
 6.)THE WALL SECTION SHOWS SLAB ON
 GRADE, A NOTE ON THE PLAN STATES 12"
 MINUMUM FROM GRADE TO JOIST.CLARIFY.
  
 7.)THE PLAN SHOWS A 37X50 5/8" S/H AS
 AN EGRESS WINDOW.THIS DIMENSION DOES
 NOT NORMALLY MEET EMERGENCY EGRESS
 REQUIREMENTS FBC1005.4.CLARIFY.
  
 8.)THE TEST REPORT PROVIDED WAS FOR A
 HORIZONTAL SLIDER, IMPACT.THE PLAN
 SPECIFIES SINGLE HUNG.BOTH SHOULD BE
 CONSISTENT.
  
  
  