| 2005-02-09 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)FLOOR LEVELING IS ON THE PLAN, |
| | PLAN |
| | SPECIFIES SHUTTERS.NEITHER IS ON THE |
| | APPLICATION.PLEASE PROVIDE A |
| | REASONABLE VALUE FOR THE JOB (NOT THE |
| | VALUE OF YOUR SERVICES; VALUE IS TO |
| | INCLUDE MATERIALS AND LABOR AS A PERMIT |
| | WAS NOT APPLIED FOR PREVIOUSLY FOR THE |
| | WINDOWS). |
| | |
| | |
| | 2.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3.)AS PER CONVERSATION WITH |
| | CONTRACTOR, WINDOWS WERE INSTALLED |
| | (APPARENTLY WITHOUT A PERMIT) IMPROPERLY |
| | BY OTHERS.PLEASE PROVIDE TEST REPORTS |
| | AND FLORIDA OR LOCAL PRODUCT APPROVALS |
| | FOR THE FOLLOWING, AS PER THE PLAN: |
| | SINGLE HUNG WINDOWS |
| | MULLIONS |
| | IMPACT PROTECTION (UNLESS WINDOWS ARE |
| | IMPACT GLASS) |
| | FIXED WINDOW |
| | |
| | 4.)PROVIDE A LEGIBLE SEAL, |
| | FAC61G1-15. |
| | |
| | 5.)THE STRUCTURAL NOTES #13 AND BUCK |
| | DETAIL CONFLICT.PLEASE PROVIDE AN |
| | ATTACHMENT DETAIL OR SPEC WITH SPACING. |
| | (CAN'T HAVE 1 1/4" EMBEDMENT WITH A 2 |
| | 1/4" TAPCON ON A 2X4 BUCK.) |
| | |
| | 6.)THE WALL SECTION SHOWS SLAB ON |
| | GRADE, A NOTE ON THE PLAN STATES 12" |
| | MINUMUM FROM GRADE TO JOIST.CLARIFY. |
| | |
| | 7.)THE PLAN SHOWS A 37X50 5/8" S/H AS |
| | AN EGRESS WINDOW.THIS DIMENSION DOES |
| | NOT NORMALLY MEET EMERGENCY EGRESS |
| | REQUIREMENTS FBC1005.4.CLARIFY. |
| | |
| | 8.)THE TEST REPORT PROVIDED WAS FOR A |
| | HORIZONTAL SLIDER, IMPACT.THE PLAN |
| | SPECIFIES SINGLE HUNG.BOTH SHOULD BE |
| | CONSISTENT. |
| | |
| | |
| | |