| Plan Review Notes For Permit 05020170 |
| Permit Number |
05020170 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-07 00:00:00 | | | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1}THERE IS A NOTE ON THE PLAN THAT | | | STATES "MAIN BREAKER AND ANOTHER THAT | | | SAYS MAIN LUG, PLEASE CLARIFY. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR THE | | | EXISTING SERVICE AND INDICATE THE SIZE | | | OF SAME. SHOW CALCS FOR THE 150 AMP | | | PANEL ON PLAN. | | | | | | 3} THE EXIT LIGHTS SHOWN ON THE PANEL | | | SCHEDULE CIRCUIT #7, AND LIGHTING ON | | | OTHER CIRCUITS DO NOT SEEM TO COMPLY | | | WITH ARTICLE 700.18, ALSO 700.12(E). | | | PLEASE SHOW COMPLIANCE, USE A FLOOR PLAN | | | INDICATING LIGHT CIRCUIT NUMBERS IF | | | NECESSARY. | | | | | | 4} THE NOTE STATING THE LOAD CENTER | | | LOCATION ON THE 2ND FLOOR SEEMS TO | | | INDICATE THE PANEL BEING REFED IS ON A | | | DIFFERENT LEVEL. IF NEW CONDUIT IS | | | PENETRATING FIRE SEPARATIONS, SHOW | | | STOPPING METHOD. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL, | | | OR IF THE CONTRACTOR WOULD LIKE A | | | MEETING TO DISCUSS ANY OF THE COMMENTS, | | | CALL | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|