Plan Review Notes For Permit 05020155
Permit Number 05020155
Review Stop E
Sequence Number 6
Notes
Date Text
2007-05-17 12:20:45 
  
 REVISION DENIED
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE 350 MCM SERVICE CONDUCTORS MUSTTERMINATE IN
 350 AMP OVERCURRENT PROTECTION. 400 AMP IS ON THE PLAN.
 SEE 240.6,310.15(B)(6) AND 230.90(A).
  
 2} PLEASE PROVIDE A PANEL SCHEDULE FOR THE 400 AMP
 DISCONNECT SO THE OCP FOR THE 200 AMP FEEDERS CAN BE
 REVIEWED.
  
 3}PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 4}AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED
 FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER
 250.118, SIZED PER 250.122. THEY ARE OMITTED FROM THE
 PLAN.
  
 5} THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH
 250.66, 1/0 CU. MINIMUM.
  
 6} THE FEED TO PANEL "C" IS NOT LISTED ON PANEL "B"
 SCHEDULE. VERIFYTHE FEED IS 2/0 CONDUCTORS TO THE 100
 AMP SUB PANEL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.