| Plan Review Notes For Permit 05020155 |
| Permit Number |
05020155 |
|
| Review Stop |
E |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2007-05-17 12:20:45 | | | | | | | REVISION DENIED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1} THE 350 MCM SERVICE CONDUCTORS MUSTTERMINATE IN | | | 350 AMP OVERCURRENT PROTECTION. 400 AMP IS ON THE PLAN. | | | SEE 240.6,310.15(B)(6) AND 230.90(A). | | | | | | 2} PLEASE PROVIDE A PANEL SCHEDULE FOR THE 400 AMP | | | DISCONNECT SO THE OCP FOR THE 200 AMP FEEDERS CAN BE | | | REVIEWED. | | | | | | 3}PER 110.9 AND 110.10: OBTAIN THE | | | AVAILABLE FAULT CURRENT AT THE UTILITY | | | AND CALCULATE THE SAME AT THE EQUIPMENT. | | | INDICATE THE AIC RATING FOR THE | | | EQUIPMENT IS EQUAL TO OR GREATER THAN | | | THE AVAILABLE FAULT. | | | | | | 4}AN EQUIPMENT GROUNDING CONDUCTOR MUST BE INSTALLED | | | FROM THE FIRST MEANS OF DISCONNECT TO THE PANEL PER | | | 250.118, SIZED PER 250.122. THEY ARE OMITTED FROM THE | | | PLAN. | | | | | | 5} THE EQUIPMENT GROUNDING CONDUCTOR MUST COMPLY WITH | | | 250.66, 1/0 CU. MINIMUM. | | | | | | 6} THE FEED TO PANEL "C" IS NOT LISTED ON PANEL "B" | | | SCHEDULE. VERIFYTHE FEED IS 2/0 CONDUCTORS TO THE 100 | | | AMP SUB PANEL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW. | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|