| 2006-08-03 00:00:00 | ON PAGE E1 PANEL A ON RISER IS IN GARAGE | | | AND ON PLAN IT IS IN THE PANTRY OFF THE | | | KITCHEN. | | | | | | THE PANEL IN THE GARAGE THAT COMES OFF | | | THE GUTTER SHOWN AS PANEL "A" DOES IT | | | HAVE A MAIN BREAKER?THE PLAN DOES NOT | | | SHOW IT!!!!!!!!!!! | | | | | | THE GUTTER EXISTING OR NOT MUST BE SIZED | | | INACCORDANCE WITH THE CODE. | | | | | | NEW OFFICE ON SECOND FLOOR WILL REQUIRE | | | ARC FAULT PROTECTION BECAUSE IT COULD BE | | | TURNED INTO A BEDROOM IF THIS OWNER | | | SELLS. PLEASE INDICATE ALL ARC FAULT | | | BREAKERS IN THE PANEL(S). | | | | | | NO WIRE SIZES SHOWN ON RISER TO GUTTER | | | AND PANEL "A" | | | | | | STEAM UNIT? UNIT SHOWS 5000W THIS CAN | | | NOT BE PUT ON A 20A BREAKER. | | | | | | PANEL SCHEDULE FOR "A SHOWS 15,000 WATTS | | | ON THE GENERAL LIGHTING CIRCUITS. | | | | | | QUESTIONS 644-7291JAKE | | | | | | |
|