| 2006-07-06 00:00:00 | |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} PROVIDE A LOAD CALCULATION PER |
| | 220.31, INCLUDE ADDED LOADS. SHOW |
| | ELEVATOR CIRCUITING AS WELL. |
| | |
| | 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC |
| | AND 106.3.5.4(8) FBC, ALL PANELS. |
| | |
| | 3} THE RISER INDICATES A NEW METER, SHOW |
| | THE GROUNDING ELECTRODE SYSTEM AND SIZE |
| | PER 250.50 AND 250.66. |
| | |
| | 4} PLACE THE GUTTER, SHOWN ON THE RISER, |
| | ON THE PLAN AT LOCATION. |
| | |
| | 5} INDICATE WHAT THE 200 AMP DISCONNECT |
| | ON THE RISER AND LOCATED IN THE GARAGE, |
| | SERVES. SHOW CONNECTIONS ON RISER. |
| | |
| | 6} THE DISCONNECTING MEANS MUST COMPLY |
| | WITH 225.32. IT IS UNCLEAR WHETHER THE |
| | FEEDERS TO THE PANELS ARE UNDER THE |
| | SLAB. IF NOT A DISCONNECT WOUD BE |
| | REQUIRED AT THE METER, SINCE THE PANELS |
| | ARE NOT BACK TO BACK, THEREFORE NOT AT |
| | THE NEAREST POINT OF ENTRANCE. |
| | |
| | 7} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE SERVICE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 8} 210.63 HEATING, AIR-CONDITIONING, AND |
| | REFRIGERATION EQUIPMENT OUTLET. |
| | A 125-VOLT, SINGLE-PHASE, 15- OR |
| | 20-AMPERE-RATED RECEPTACLE OUTLET SHALL |
| | BE INSTALLED AT AN ACCESSIBLE LOCATION |
| | FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE SHALL BE |
| | LOCATED ON THE SAME LEVEL AND WITHIN 7.5 |
| | M (25 FT) OF THE HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION |
| | EQUIPMENT. THE RECEPTACLE OUTLET SHALL |
| | NOT BE CONNECTED TO THE LOAD SIDE OF THE |
| | EQUIPMENT DISCONNECTING MEANS. |
| | |
| | 9} PLEASE SEE ALL SMOKE DETECTORS MUST |
| | BE INTERCONNECTED, WITH A BATTERY BACK |
| | UP, PER R313 FBC. ALSO ARC FAULT PER |
| | 210.12. PLEASE LOCATE DETECTORS ON THE |
| | PLAN SO LOCATION COMPLIANCE PER 313.1 |
| | CAN BE REVIEWED. |
| | |