2006-07-06 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS. SHOW
 ELEVATOR CIRCUITING AS WELL.
  
 2} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC, ALL PANELS.
  
 3} THE RISER INDICATES A NEW METER, SHOW
 THE GROUNDING ELECTRODE SYSTEM AND SIZE
 PER 250.50 AND 250.66.
  
 4} PLACE THE GUTTER, SHOWN ON THE RISER,
 ON THE PLAN AT LOCATION.
  
 5} INDICATE WHAT THE 200 AMP DISCONNECT
 ON THE RISER AND LOCATED IN THE GARAGE,
 SERVES. SHOW CONNECTIONS ON RISER.
  
 6} THE DISCONNECTING MEANS MUST COMPLY
 WITH 225.32. IT IS UNCLEAR WHETHER THE
 FEEDERS TO THE PANELS ARE UNDER THE
 SLAB. IF NOT A DISCONNECT WOUD BE
 REQUIRED AT THE METER, SINCE THE PANELS
 ARE NOT BACK TO BACK, THEREFORE NOT AT
 THE NEAREST POINT OF ENTRANCE.
  
 7} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE SERVICE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 8} 210.63 HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT OUTLET.
 A 125-VOLT, SINGLE-PHASE, 15- OR
 20-AMPERE-RATED RECEPTACLE OUTLET SHALL
 BE INSTALLED AT AN ACCESSIBLE LOCATION
 FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE SHALL BE
 LOCATED ON THE SAME LEVEL AND WITHIN 7.5
 M (25 FT) OF THE HEATING,
 AIR-CONDITIONING, AND REFRIGERATION
 EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE
 EQUIPMENT DISCONNECTING MEANS.
  
 9} PLEASE SEE ALL SMOKE DETECTORS MUST
 BE INTERCONNECTED, WITH A BATTERY BACK
 UP, PER R313 FBC. ALSO ARC FAULT PER
 210.12. PLEASE LOCATE DETECTORS ON THE
 PLAN SO LOCATION COMPLIANCE PER 313.1
 CAN BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  