Plan Review Notes
Plan Review Notes For Permit 05011550
Permit Number 05011550
Review Stop B
Sequence Number 3
Notes
Date Text
2006-04-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 FROM PREVIOUS REVIEW, NUMBERING TO
 REMAIN THE SAME FOR CONSISTENCY
  
 1. ADDRESSED.
  
 2. DECLARE AN OCCUPANCY AND BUILDING
 TYPE FOR FBC TABLE 600 AND TABLE 500
 REVIEW.PLEASE NOTE THAT FOR TABLE 600
 REVIEW THE FLORIDA EAST COAST RAIL ROAD
 IS CONSIDERED PRIVATE PROPERTY.
  
 (SECOND REVIEW) NOT ADDRESSED.SEE
 CHAPTER 3, CHAPTER
 6, CHAPTER 5.PROVIDE INFORMATION ABOUT
 WHAT WILL BE STORED IN THIS BUILDING.
  
 (THIRD REVIEW) NOT ADDRESSED PROPERLY.
 A RESPONSE LETTER FROM THE ARCHITECT
 STATING THAT THERE ARE NO OPENINGS
 WITHIN 3' DOES NOT SHOW CODE COMPLIANCE.
 SHOW THE PROPERTY LINE IN RELATION TO
 THE BUILDING OPENINGS ON THE PLANS.
 THERE IS A DOOR NEAR THE SOUTH EAST
 CORNER WHICH MUST BE OVER THREE FEET
 FROM THE PROPERTY LINE PER TABLE 600.
 ALSO SHOW THE PROPERTY LINE ON THE
 FOUNDATION PLAN.IT APPEARS THAT ONE OF
 THE FOOTINGS CROSSES OVER THE PROPERTY
 LINE.
  
 PROVIDE INFORMATION IN REGARDS TO WHAT
 WILL BE STORED IN THE BUILDING (NOT
 ADDRESSED FROM LAST REVIEW, SEE FBC312,
 FBC308.
  
 DECLARE A SUBCLASSIFICATION, FBC312.
  
 THE OCCUPANCY NUMBERS DECLARED ARE LESS
 THAN THE FBC TABLE 1003.1, FBC 1003.1.
  
 3. ADDRESSED.
  
 4. THE WALL PANELS, ROOF PANELS, DOORS,
 WINDOWS, IMPACT PROTECTION, AND OVERHEAD
 DOOR REQUIRE FLORIDA OR LOCAL PRODUCT
 APPROVAL, FAC9B72.
 WWW.FLORIDABUILDING.ORG FOR MORE
 INFORMATION.
  
 (SECOND REVIEW)NOT ADDRESSED.A
 PERMIT CANNOT BE
 ISSUED UNTIL THIS ITEM IS ADDRESSED.
 PLEASE SEE FAC9B72.
  
 (THIRD REVIEW)A STATE PRODUCT APPROVAL
 2001 WAS SUBMITTED FOR WEDGCOR.NO
 OTHER STATE APPROVALS PROVIDED.PLEASE
 SEE FAC9B72.IF A STATE PRODUCT
 APPROVAL IS NOT AVAILABLE, PLEASE ADVISE
 AND A LOCAL PRODUCT APPROVAL WILL BE
 ISSUED USING THE NOA.
  
 5. ADDRESSED.
  
 6. ADDRESSED.
  
 7. PROVIDE THE INFORMATION REQUIRED BY
 FBC1606.1.7 ON BOTH PLANS.
  
 (SECOND REVIEW) NOT ADDRESSED.CODE
 COMPLIANCE CANNOT
 BE DETERMINED IF THERE WIND DESIGN
 CRITERIA IS NOT STATED.
  
 (THIRD REVIEW)
  
 WIND PRESSURES FOR THE OPENINGS HAVE
 BEEN HANDWRITTEN ON THE PLAN.PLEASE
 CLOUD AND INITIAL.OTHER INFORMATION IS
 STILL LACKING.SEE FBC1606.1.7.THIS
 IS TO BE INCLUDED ON BOTH SETS OF PLANS;
 THE PLAN PREPARED BY ROBERT L. BELL
 ARCHITECT (OR THE PLANS PREPARED BY
 NALYWAJKO & ASSOCIATES) AND THE PLAN FOR
 THE WEDGCOR BUILDING.
  
 THIS IS THE THIRD REQUEST FOR MR.
 RICHARD JOYCE, PE TO PROVIDE WIND DESIGN
 INFORMATION.
  
 8. ADDRESSED.
  
 9. ADDRESSED.
  
 10. THERE ARE TO BE TWO INDEPENDENT
 EXITS, FBC1004.2.
  
 THERE ARE TO BE TWO ACCESSIBLE EXITS,
 FBC11-4.1.3(9).SEE DEFINITION OF
 EGRESS IN CHAPTER 11.SHOW COMPLIANCE
 ON THE PLAN.IT IS STILL NOT CLEAR AS
 TO WHICH DOORS ARE ACCESSIBLE.YOU
 INDICATE 'ACCESSIBLE ROUTE' WITH NO
 ELEVATIONS.THE PAVING & DRAINAGE PLAN
 SHOWS A FFE OF 17-17.6 FOR THE BUILDING,
 AND 18 SHOWN IN THE PARKING AREA.IS
 THE X SUPPOSED TO BE OVER THE CURB, NOT
 THE PAVEMENT?THE SLOPE OF THE SIDEWALK
 IS NOT CLEAR.THE CURB IS NOT
 CONTINUOUS SO THERE SHOULD BE AN
 ELEVATION CHANGE, BUT THAT ISN'T CLEAR.
 CLEARLY SHOW WHICH DOORS
 ARE ACCESSIBLE, AND THAT THEYARE
 INDEPENDENT EXITS REMOTELY LOCATED
 FBC1004.1.4, LEADING TO THE PUBLIC WAY
 AS REQUIRED BY DEFINITION, DO NOT EXCEED
 TRAVEL DISTANCE FBC TABLE 1004 OR COMMON
 PATH OF TRAVEL FBC1004.1.3.
  
 11. PROVIDE INFORMATION IN REGARDS TO
 THE ACCESSIBLE ROUTE, ACCESSIBLE
 PARKING.
  
 (SECOND REVIEW) ACCESSIBLE ROUTE NOT
 SHOWN FBC11-4.1.2(1) AND (2).
 ACCESSIBLE PARKING DOES NOT COMPLY WITH
 CITY STANDARD, SEE ATTACHED.
 SHOW ACCESSIBLE ROUTE INTO THE BUILDING.
 NO FLOOR ELEVATIONS PROVIDED.
  
 (THIRD REVIEW)PLANS SHOULD SHOW CODE
 COMPLIANCE.THERE APPEARS TO BE A 6'
 INCH ELEVATION DIFFERENCE ON THIS
 PROPERTY AND IT IS NOT CLEAR HOW THIS IS
 ADDRESSED FOR ACCESSIBILITY.STATING
 THAT SOMETHING IS AN ACCESSIBLE PATH IS
 NOT SUFFICIENT.PROVIDE ELEVATIONS,
 ELEVATION CHANGE OR SLOPE AS REQUESTED.
  
 THE PAVING & DRAINAGE PLAN ACCESSIBLE
 PARKING DETAIL DOES NOT COMPLY WITH THE
 CITY OF WPB STANDARD.
  
 12. ADDRESSED.
  
 13. ADDRESSED.
  
 14. A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 NEW COMMENTS, SECOND REVIEW:
  
 15. ADDRESSED.
  
 16. DOCUMENTS PREPARED BY AN ARCHITECT
 AND SUBMITTED FOR PUBLIC RECORD ARE TO
 BE SIGNED, SEALED, DATED ORIGINALS
 FAC61G16.
  
 (THIRD REVIEW) PLANS SUBMITTED ARE NOT
 SEALED.
  
 17. ADDRESSED.
  
 18.ADDRESSED.
  
 19.ADDRESSED.
  
 20.SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED A THIRD TIME.
  
 (THIRD REVIEW) A 4X FEE HAS BEEN
 CHARGED.NO RESUB FEE DUE FOR FOURTH
 REVIEW.
  
 NEW COMMENT, THIRD REVIEW
  
 21.CLARIFY SCOPE OF WORK.ONE PLAN
 STATES THAT THERE IS A SLAB ONLY, FLOOR
 PLAN SHOW EXISTING INTERIOR PARTITIONS,
 AND I HAVE BEEN INFORMED THAT THE
 INTERIOR PARTITIONS SHOWN AS EXISTING
 ARE NOT THERE NOW.PROVIDE DETAILS FOR
 NEW WALLS, CONNECTIONS FROM EXISTING TO
 NEW WALLS IF ANY.
  
 22.A VALUATION ADJUSTMENT HAS BEEN
 DONE (USING SBCCI VALUATION TABLE FROM
 2003).A BILL INCLUDING THE ADDITIONAL
 FEES DUE AS WELL AS THE 4X FEE CHARGED
 IS ATTACHED.THIS MUST BE PAID PRIOR TO
 RESUBMITTAL.
  
 23.EFFECTIVE JAN 1, 2006 THE SEAL FOR
 THE ENGINEER IS TO STATE "LICENSE", NOT
 "CERTIFICATE" FAC61G15-23.
  
 A COPY OF THE PLAN HAS BEEN RETAINED.
  
 WHEN RESUBMITTING, ALL CHANGES ON THE
 PLAN ARE TO BE CLEARLY INDICATED WITH
 CLOUDS AND REVISION NUMBERS.REPLACE
 ONLY SHEETS WHICH HAVE CHANGED.SUBMIT
 OLD SHEETS SEPARATELY.TO EXPEDITE PLAN
 REVIEW, PROVIDE A TRANSMITTAL LETTER
 EXPLAINING HOW EACH ITEM HAS BEEN
 ADDRESSED.