| Date |
Text |
| 2006-04-14 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | FROM PREVIOUS REVIEW, NUMBERING TO |
| | REMAIN THE SAME FOR CONSISTENCY |
| | |
| | 1. ADDRESSED. |
| | |
| | 2. DECLARE AN OCCUPANCY AND BUILDING |
| | TYPE FOR FBC TABLE 600 AND TABLE 500 |
| | REVIEW.PLEASE NOTE THAT FOR TABLE 600 |
| | REVIEW THE FLORIDA EAST COAST RAIL ROAD |
| | IS CONSIDERED PRIVATE PROPERTY. |
| | |
| | (SECOND REVIEW) NOT ADDRESSED.SEE |
| | CHAPTER 3, CHAPTER |
| | 6, CHAPTER 5.PROVIDE INFORMATION ABOUT |
| | WHAT WILL BE STORED IN THIS BUILDING. |
| | |
| | (THIRD REVIEW) NOT ADDRESSED PROPERLY. |
| | A RESPONSE LETTER FROM THE ARCHITECT |
| | STATING THAT THERE ARE NO OPENINGS |
| | WITHIN 3' DOES NOT SHOW CODE COMPLIANCE. |
| | SHOW THE PROPERTY LINE IN RELATION TO |
| | THE BUILDING OPENINGS ON THE PLANS. |
| | THERE IS A DOOR NEAR THE SOUTH EAST |
| | CORNER WHICH MUST BE OVER THREE FEET |
| | FROM THE PROPERTY LINE PER TABLE 600. |
| | ALSO SHOW THE PROPERTY LINE ON THE |
| | FOUNDATION PLAN.IT APPEARS THAT ONE OF |
| | THE FOOTINGS CROSSES OVER THE PROPERTY |
| | LINE. |
| | |
| | PROVIDE INFORMATION IN REGARDS TO WHAT |
| | WILL BE STORED IN THE BUILDING (NOT |
| | ADDRESSED FROM LAST REVIEW, SEE FBC312, |
| | FBC308. |
| | |
| | DECLARE A SUBCLASSIFICATION, FBC312. |
| | |
| | THE OCCUPANCY NUMBERS DECLARED ARE LESS |
| | THAN THE FBC TABLE 1003.1, FBC 1003.1. |
| | |
| | 3. ADDRESSED. |
| | |
| | 4. THE WALL PANELS, ROOF PANELS, DOORS, |
| | WINDOWS, IMPACT PROTECTION, AND OVERHEAD |
| | DOOR REQUIRE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG FOR MORE |
| | INFORMATION. |
| | |
| | (SECOND REVIEW)NOT ADDRESSED.A |
| | PERMIT CANNOT BE |
| | ISSUED UNTIL THIS ITEM IS ADDRESSED. |
| | PLEASE SEE FAC9B72. |
| | |
| | (THIRD REVIEW)A STATE PRODUCT APPROVAL |
| | 2001 WAS SUBMITTED FOR WEDGCOR.NO |
| | OTHER STATE APPROVALS PROVIDED.PLEASE |
| | SEE FAC9B72.IF A STATE PRODUCT |
| | APPROVAL IS NOT AVAILABLE, PLEASE ADVISE |
| | AND A LOCAL PRODUCT APPROVAL WILL BE |
| | ISSUED USING THE NOA. |
| | |
| | 5. ADDRESSED. |
| | |
| | 6. ADDRESSED. |
| | |
| | 7. PROVIDE THE INFORMATION REQUIRED BY |
| | FBC1606.1.7 ON BOTH PLANS. |
| | |
| | (SECOND REVIEW) NOT ADDRESSED.CODE |
| | COMPLIANCE CANNOT |
| | BE DETERMINED IF THERE WIND DESIGN |
| | CRITERIA IS NOT STATED. |
| | |
| | (THIRD REVIEW) |
| | |
| | WIND PRESSURES FOR THE OPENINGS HAVE |
| | BEEN HANDWRITTEN ON THE PLAN.PLEASE |
| | CLOUD AND INITIAL.OTHER INFORMATION IS |
| | STILL LACKING.SEE FBC1606.1.7.THIS |
| | IS TO BE INCLUDED ON BOTH SETS OF PLANS; |
| | THE PLAN PREPARED BY ROBERT L. BELL |
| | ARCHITECT (OR THE PLANS PREPARED BY |
| | NALYWAJKO & ASSOCIATES) AND THE PLAN FOR |
| | THE WEDGCOR BUILDING. |
| | |
| | THIS IS THE THIRD REQUEST FOR MR. |
| | RICHARD JOYCE, PE TO PROVIDE WIND DESIGN |
| | INFORMATION. |
| | |
| | 8. ADDRESSED. |
| | |
| | 9. ADDRESSED. |
| | |
| | 10. THERE ARE TO BE TWO INDEPENDENT |
| | EXITS, FBC1004.2. |
| | |
| | THERE ARE TO BE TWO ACCESSIBLE EXITS, |
| | FBC11-4.1.3(9).SEE DEFINITION OF |
| | EGRESS IN CHAPTER 11.SHOW COMPLIANCE |
| | ON THE PLAN.IT IS STILL NOT CLEAR AS |
| | TO WHICH DOORS ARE ACCESSIBLE.YOU |
| | INDICATE 'ACCESSIBLE ROUTE' WITH NO |
| | ELEVATIONS.THE PAVING & DRAINAGE PLAN |
| | SHOWS A FFE OF 17-17.6 FOR THE BUILDING, |
| | AND 18 SHOWN IN THE PARKING AREA.IS |
| | THE X SUPPOSED TO BE OVER THE CURB, NOT |
| | THE PAVEMENT?THE SLOPE OF THE SIDEWALK |
| | IS NOT CLEAR.THE CURB IS NOT |
| | CONTINUOUS SO THERE SHOULD BE AN |
| | ELEVATION CHANGE, BUT THAT ISN'T CLEAR. |
| | CLEARLY SHOW WHICH DOORS |
| | ARE ACCESSIBLE, AND THAT THEYARE |
| | INDEPENDENT EXITS REMOTELY LOCATED |
| | FBC1004.1.4, LEADING TO THE PUBLIC WAY |
| | AS REQUIRED BY DEFINITION, DO NOT EXCEED |
| | TRAVEL DISTANCE FBC TABLE 1004 OR COMMON |
| | PATH OF TRAVEL FBC1004.1.3. |
| | |
| | 11. PROVIDE INFORMATION IN REGARDS TO |
| | THE ACCESSIBLE ROUTE, ACCESSIBLE |
| | PARKING. |
| | |
| | (SECOND REVIEW) ACCESSIBLE ROUTE NOT |
| | SHOWN FBC11-4.1.2(1) AND (2). |
| | ACCESSIBLE PARKING DOES NOT COMPLY WITH |
| | CITY STANDARD, SEE ATTACHED. |
| | SHOW ACCESSIBLE ROUTE INTO THE BUILDING. |
| | NO FLOOR ELEVATIONS PROVIDED. |
| | |
| | (THIRD REVIEW)PLANS SHOULD SHOW CODE |
| | COMPLIANCE.THERE APPEARS TO BE A 6' |
| | INCH ELEVATION DIFFERENCE ON THIS |
| | PROPERTY AND IT IS NOT CLEAR HOW THIS IS |
| | ADDRESSED FOR ACCESSIBILITY.STATING |
| | THAT SOMETHING IS AN ACCESSIBLE PATH IS |
| | NOT SUFFICIENT.PROVIDE ELEVATIONS, |
| | ELEVATION CHANGE OR SLOPE AS REQUESTED. |
| | |
| | THE PAVING & DRAINAGE PLAN ACCESSIBLE |
| | PARKING DETAIL DOES NOT COMPLY WITH THE |
| | CITY OF WPB STANDARD. |
| | |
| | 12. ADDRESSED. |
| | |
| | 13. ADDRESSED. |
| | |
| | 14. A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | NEW COMMENTS, SECOND REVIEW: |
| | |
| | 15. ADDRESSED. |
| | |
| | 16. DOCUMENTS PREPARED BY AN ARCHITECT |
| | AND SUBMITTED FOR PUBLIC RECORD ARE TO |
| | BE SIGNED, SEALED, DATED ORIGINALS |
| | FAC61G16. |
| | |
| | (THIRD REVIEW) PLANS SUBMITTED ARE NOT |
| | SEALED. |
| | |
| | 17. ADDRESSED. |
| | |
| | 18.ADDRESSED. |
| | |
| | 19.ADDRESSED. |
| | |
| | 20.SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW WILL BE CHARGED IF THE |
| | COMMENTS ARE NOT ADDRESSED A THIRD TIME. |
| | |
| | (THIRD REVIEW) A 4X FEE HAS BEEN |
| | CHARGED.NO RESUB FEE DUE FOR FOURTH |
| | REVIEW. |
| | |
| | NEW COMMENT, THIRD REVIEW |
| | |
| | 21.CLARIFY SCOPE OF WORK.ONE PLAN |
| | STATES THAT THERE IS A SLAB ONLY, FLOOR |
| | PLAN SHOW EXISTING INTERIOR PARTITIONS, |
| | AND I HAVE BEEN INFORMED THAT THE |
| | INTERIOR PARTITIONS SHOWN AS EXISTING |
| | ARE NOT THERE NOW.PROVIDE DETAILS FOR |
| | NEW WALLS, CONNECTIONS FROM EXISTING TO |
| | NEW WALLS IF ANY. |
| | |
| | 22.A VALUATION ADJUSTMENT HAS BEEN |
| | DONE (USING SBCCI VALUATION TABLE FROM |
| | 2003).A BILL INCLUDING THE ADDITIONAL |
| | FEES DUE AS WELL AS THE 4X FEE CHARGED |
| | IS ATTACHED.THIS MUST BE PAID PRIOR TO |
| | RESUBMITTAL. |
| | |
| | 23.EFFECTIVE JAN 1, 2006 THE SEAL FOR |
| | THE ENGINEER IS TO STATE "LICENSE", NOT |
| | "CERTIFICATE" FAC61G15-23. |
| | |
| | A COPY OF THE PLAN HAS BEEN RETAINED. |
| | |
| | WHEN RESUBMITTING, ALL CHANGES ON THE |
| | PLAN ARE TO BE CLEARLY INDICATED WITH |
| | CLOUDS AND REVISION NUMBERS.REPLACE |
| | ONLY SHEETS WHICH HAVE CHANGED.SUBMIT |
| | OLD SHEETS SEPARATELY.TO EXPEDITE PLAN |
| | REVIEW, PROVIDE A TRANSMITTAL LETTER |
| | EXPLAINING HOW EACH ITEM HAS BEEN |
| | ADDRESSED. |