| 2005-03-01 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) INDICATE THE OCCUPANCY OF THE | | | BUILDING AS THIS WILL SET THE | | | REQUIREMENTS FOR MINIMUM FIXTURE | | | REQUIREMENTS. FURTHER COMMENTS MAY BE | | | ADDED DEPENDING ON THE RESPONSE FROM | | | THIS COMMENT. SECTION 104.2.1. | | | 2) AT THE MINIMUM A DRINKING FOUNTAIN IS | | | REQUIRED PER TABLE 403.1, AND POSSIBLY A | | | SERVICE SINK. | | | 3) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE TO THE BUILDING. SECTION | | | 608.13.2. | | | 4) THE FOLLOWING INFORMATION IS REQUIRED | | | TO SHOW COMPLIANCE WITH CHAPER 11: | | | A) CLEAR FLOOR SPACE 11-4.16.2. | | | B) HEIGHT & CLEARANCES 11-4.19.2. - 29" | | | CLEARANCE REQUIRED. 28" CLEARANCE SHOWN | | | 0N PLANS. | | | C) CLEAR FLOOR SPACE 11-4.19.3 | | | D) EXPOSED PIPES & SURFACES 11-4.19.4 - | | | INDICATE IF THE PIPES WILL BE INSULATED | | | OR IF THE PIPES ARE FRAMED AND COVERED | | | WITH A PANEL. | | | E) FAUCETS 11-4.19.5 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|