Plan Review Notes For Permit 05011550
Permit Number 05011550
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) INDICATE THE OCCUPANCY OF THE
 BUILDING AS THIS WILL SET THE
 REQUIREMENTS FOR MINIMUM FIXTURE
 REQUIREMENTS. FURTHER COMMENTS MAY BE
 ADDED DEPENDING ON THE RESPONSE FROM
 THIS COMMENT. SECTION 104.2.1.
 2) AT THE MINIMUM A DRINKING FOUNTAIN IS
 REQUIRED PER TABLE 403.1, AND POSSIBLY A
 SERVICE SINK.
 3) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE TO THE BUILDING. SECTION
 608.13.2.
 4) THE FOLLOWING INFORMATION IS REQUIRED
 TO SHOW COMPLIANCE WITH CHAPER 11:
 A) CLEAR FLOOR SPACE 11-4.16.2.
 B) HEIGHT & CLEARANCES 11-4.19.2. - 29"
 CLEARANCE REQUIRED. 28" CLEARANCE SHOWN
 0N PLANS.
 C) CLEAR FLOOR SPACE 11-4.19.3
 D) EXPOSED PIPES & SURFACES 11-4.19.4 -
 INDICATE IF THE PIPES WILL BE INSULATED
 OR IF THE PIPES ARE FRAMED AND COVERED
 WITH A PANEL.
 E) FAUCETS 11-4.19.5
  