| Date |
Text |
| 2006-03-22 00:00:00 | IN ELEC FOR THE FIRST REVIEW. |
| | ****** UNSAT ****** |
| | |
| | ** PLEASE KNOW, THIS IS THE FIRST TIME |
| | ELECTRICAL PLANS ARE BEING SUBMITTED FOR |
| | REVIEW. |
| | |
| | |
| | 1)NOTE: PLEASE KNOW, THE PERMIT |
| | VALUATION SHALL BE ADJUSTED AND |
| | INCREASED FOR TOTAL SCOPE OF. PLEASE |
| | KNOW, THE EXISTING PARTIAL WALL ON NORTH |
| | AND EAST ELEVATION WAS VISUALLY VERIFIED |
| | FOR SCOPE OF WORK. |
| | PLEASE SEE FBC ADMINISTRATIVE CODE |
| | SECTION, 104.6.5. |
| | PLEASE SEE COMMENTS FROM OTHER REVIEWERS |
| | AS THIS IS NO LONGER A "REPAIR", AND |
| | WILL BE REQUIRED TO COMPLY WITH FBC |
| | CHAPTER 34 |
| | ** IT IS NOTED THAT ALL ELECTRICAL |
| | SYSTEMS ARE GOING TO BE NEW. |
| | |
| | 2)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | ON PLANS. PLEASE SEE CIRCUITS FOR OH |
| | DOORS. (19). PLEASE ALSO PROVIDE HP |
| | RATINGS FOR THESE MOTORS SO THAT LOADS, |
| | AWG, AND OCP CAN BE VERIFIED. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SEE THE HAND DRAWN |
| | DELETION ON PLANS OF A/C UNITS, MUST BE |
| | SIGNED, DATED BY THE ENGINEER, HOWEVER |
| | SINCE PLANE WILLBE RE-PRINTED DUE TO |
| | COMMENTS, PLEASE REMOVE AT THAT TIME. |
| | 215.5 |
| | |
| | 4)NOTE: PLEASE INDICATE THE "TAPPED" |
| | CONDUCTOR SIZS FROM GUTTER TO MAINS. |
| | PLEASE KNOW, NO "EUIPMENT GROUNDING |
| | CONDUCTOR" IS INSTALLED UNTIL AFTER THE |
| | FIRST MEANS OF DISCONNECT. 250.6,250.24B |
| | |
| | 5)NOTE: PLEASE INDICATE THE SIZE OF THE |
| | GE CONDUCTOR. 250.66 PLEASE SEE PLANS |
| | MENTIONS TO SEE DETAIL, HOWEVER NO SIZE |
| | IS SHOWN. |
| | |
| | 6)NOTE: PLEASE REFERENCE THE 2002 NEC |
| | WHICH IS CURRENTLY IN EFFECT. |
| | |
| | 7) NOTE: PLEASE SEE THE POSSIBILITY OF |
| | NOTES PERTAINING TO THE MEANS OF EGRESS |
| | IN REAR OF BLDG(EAST ) WHICH SHOWS |
| | EGRESS TO FEC EASEMENT WHICH IS NOT THE |
| | PUBLIC RIGHT OF WAY. |
| | PLEASE SEE THIS MAY AFFECT ELECTRICAL.? |
| | |
| | |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | REVIEWER(S) WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLYINSERT NEW REVISED SHEETS INTO |
| | TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE KNOW, ONE COPY OF ANY |
| | OLD/VOIDED SHEETS SHALL BE SUBMITTED FOR |
| | REFERENCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW AND IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |