Plan Review Notes
Plan Review Notes For Permit 05011539
Permit Number 05011539
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-22 00:00:00** UNSAT **
  
 PLEASE SEE SOME ITEMS FROM PREVIOUS
 REVIEW.
  
 1)NOTE: OK.
  
 2)NOTE: OK
  
 3)NOTE: NO, PLEASE SEE 250.32,250.50 FOR
 GROUNDING AT DETACHED BLDG. PLEASE SEE
 GROUNDING RISER FOR SERVICE BLDG SHOWS
 ATTACHMENT FOR GROUND RODS ONLY.
 PLEASE SEE ANY METAL CWP AND FOOTER
 STEEL IS ALSO REQUIRED.
  
 4)NOTE:OK
  
 5)NOTE: OK, HOWEVER PLEASE VERIFY WHERE
 NOTE IS LOCATED FOR EXCEPTION METHOD AND
 "LOCK-OFF TO BE PROVIDED. 700.12E
  
 6)NOTE: SUBMITTED SPECS HOWEVER, PLEASE
 SEE A CIRCUIT FOR A BATTERY CHARGER HAS
 NOT BEEN ADDED AT FIRE PUMP LOCATION??
 PLEASE SEESPECS FOR FIRE PUMP AND FIRE
 PUMP CONTROLLER. THIS SHOWS FULL LOAD
 CURRENT AND LOCKED ROTOR OTHER THAN WHAT
 IS REQUIRED UNDER NEC 430 TABLES.
 PLEASE KNOW, THE NEC SHALL BE USED FOR
 SIZING.
 PLEASE BE SURE A NOTE ON RISER DIAGRMA
 STATES REQUIREMENT FOR LOCKED ROTOR OCP.
  
 7)NOTE: OK
  
 8)NOTE: OK
  
 NEW NOTES:
  
 1)NOTE: PLEASE SEE BLDG REVIEW COMMENT
 REQUESTED THAT GARAGE SERVICE BLDG BE
 UNDER SEPARATE PERMIT, HOWEVER RESPONSE
 LETTER MENTIONS PLANS REMOVED BUT THEY
 WERE NOT SUBMITTED UNDER SEPARATE
 PERMIT.
  
 2)NOTE:PLEASE CLARIFY FIRE RATING FOR IT
 ROOM. UNDER NFPA-75CHAPTER 3
 NEC 645.2
  
 3)NOTE: PLEASE SEE SIGNAGE WILL BE
 REQUIRED AT MAIN ENTRANCE FOR LOCATION
 OF ADDITIONAL KNOW BOX TO BE LOCATTED AT
 THE NEAREST ENTRANCE TO LOCATION OF MDP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  