| Date |
Text |
| 2005-04-22 00:00:00 | ** UNSAT ** |
| | |
| | PLEASE SEE SOME ITEMS FROM PREVIOUS |
| | REVIEW. |
| | |
| | 1)NOTE: OK. |
| | |
| | 2)NOTE: OK |
| | |
| | 3)NOTE: NO, PLEASE SEE 250.32,250.50 FOR |
| | GROUNDING AT DETACHED BLDG. PLEASE SEE |
| | GROUNDING RISER FOR SERVICE BLDG SHOWS |
| | ATTACHMENT FOR GROUND RODS ONLY. |
| | PLEASE SEE ANY METAL CWP AND FOOTER |
| | STEEL IS ALSO REQUIRED. |
| | |
| | 4)NOTE:OK |
| | |
| | 5)NOTE: OK, HOWEVER PLEASE VERIFY WHERE |
| | NOTE IS LOCATED FOR EXCEPTION METHOD AND |
| | "LOCK-OFF TO BE PROVIDED. 700.12E |
| | |
| | 6)NOTE: SUBMITTED SPECS HOWEVER, PLEASE |
| | SEE A CIRCUIT FOR A BATTERY CHARGER HAS |
| | NOT BEEN ADDED AT FIRE PUMP LOCATION?? |
| | PLEASE SEESPECS FOR FIRE PUMP AND FIRE |
| | PUMP CONTROLLER. THIS SHOWS FULL LOAD |
| | CURRENT AND LOCKED ROTOR OTHER THAN WHAT |
| | IS REQUIRED UNDER NEC 430 TABLES. |
| | PLEASE KNOW, THE NEC SHALL BE USED FOR |
| | SIZING. |
| | PLEASE BE SURE A NOTE ON RISER DIAGRMA |
| | STATES REQUIREMENT FOR LOCKED ROTOR OCP. |
| | |
| | 7)NOTE: OK |
| | |
| | 8)NOTE: OK |
| | |
| | NEW NOTES: |
| | |
| | 1)NOTE: PLEASE SEE BLDG REVIEW COMMENT |
| | REQUESTED THAT GARAGE SERVICE BLDG BE |
| | UNDER SEPARATE PERMIT, HOWEVER RESPONSE |
| | LETTER MENTIONS PLANS REMOVED BUT THEY |
| | WERE NOT SUBMITTED UNDER SEPARATE |
| | PERMIT. |
| | |
| | 2)NOTE:PLEASE CLARIFY FIRE RATING FOR IT |
| | ROOM. UNDER NFPA-75CHAPTER 3 |
| | NEC 645.2 |
| | |
| | 3)NOTE: PLEASE SEE SIGNAGE WILL BE |
| | REQUIRED AT MAIN ENTRANCE FOR LOCATION |
| | OF ADDITIONAL KNOW BOX TO BE LOCATTED AT |
| | THE NEAREST ENTRANCE TO LOCATION OF MDP. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |