2005-05-10 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) SEE THE PREVIOUS LIST IN REGARDS TO
 ITEMS 2, 3 AND 5.THE CONTRACTOR?S
 STATEMENT IS ACKNOWLEDGED THAT THESE
 ITEMS WILL BE ADDRESSED PRIOR TO
 ISSUANCE.
  
 2.)THE ADDRESS FOR THIS PARCEL WILL BE
 5163 TYLERLAKES BLVD AS THE MAIN
 ENTRANCE IS ON TYLERLAKES.IF MY
 UNDERSTANDING IS NOT CORRECT PLEASE
 CONTACT JOHN HIGGINS TO HAVE THE ADDRESS
 REVISED, 561-822-1239. PLEASE REVISE THE
 APPLICATION TO REFLECT THE CORRECT
 ADDRESS.
  
 2.)PLEASE BE ADVISED THAT THREE COPIES
 OF ALL PLAN DOCUMENTS ARE REQUIRED.THE
 ADDITIONAL COPY IS FOR THE RESIDENT
 INSPECTOR.
  
 3.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 4.)PLEASE HAVE THE ENGINEER
 RESPONSIBLE FOR THE STRUCTURAL CALCS
 READ FAC61G15.23.002.THE TITLE BLOCK
 IS NOT COMPLIANT.THERE IS ANOTHER
 ENGINEER?S NAME (WILLIAM H. SCHMIDT,
 STRUCTURAL ENGINEER) ON SOME OF THE
 CALCS CONTAINED IN THE BOOK TITLED
 ?STRUCTURAL CALCULATIONS FOR FRITO-LAY
 WEST PALM BEACH, FL?.IF SEALING AN
 INDEX OR COVER SHEET IN LIEU OF SEALING
 EACH SHEET, THE COVER SHEET SHOULD
 CONTAIN MORE INFORMATION THAN JUST THE
 JOB NAME.THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE
 DOCUMENT SHOULD INCORPORATED INTO EACH
 SHEET.A TITLE BLOCK IS STILL REQUIRED
 ON EACH SHEET EVEN IF ONLY THE COVER
 SHEET IS SEALED.PLEASE READ THE
 SECTION AND SUBMIT CALCS WHICH ARE
 COMPLIANT WITH THE BOARD RULES.THERE
 MAY BE OTHER REQUIREMENTS WHICH I HAVE
 NOT SPECIFICALLY REFERRED TO.
  
 5.)THE STRUCTURAL CALCS ?SQUARE
 FOOTING DESIGN? HAS A 1.33 DURATION
 FACTOR.THE ?GENERAL FOOTING? HAS A
 1.33 SHORT TERM INCREASE.PAGE CP5 ACI
 FACTORS REFERS TO THE 1.3 SHORT TERM
 INCREASE.SHEET G1 WIND SPEED CALC ALSO
 USES 1.3 AS A MULTIPLIER; UNCLEAR TO ME
 WHAT THIS NUMBER IS.I WAS UNABLE TO
 FIND EITHER THE SHORT TERM OR THE
 DURATION FACTOR LOAD INCREASES IN
 ACI318-02.PLEASE CLARIFY.
  
 6.)THE CALCS FOR THE STEEL BUILDING
 ALSO REQUIRES A TITLE BLOCK.
  
 7.)PLEASE HAVE MR. MARK VANNICE, PE
 READ FAC61G15-23.002.THE ROOF DECK
 CALCS ARE INCLUDED ON THE COVER SHEET
 SEALED BY MR. GURLEY, BUT HAS AN INK
 SEAL (AS WELL AS BEING SIGNED AND DATED)
 BY MR. VANNICE.IT IS NOT CLEAR WHO IS
 RESPONSIBLE FOR THESE CALCS.THE SEAL
 IS TO BE A RAISED SEAL AND A TITLE BLOCK
 IS REQUIRED IF MR. VANNICE IS
 RESPONSIBLE.
  
 8.)STRUCTURAL DRAWINGS FOR THE STEEL
 BUILDING INDICATE WIND DESIGN PRESSURE
 OF COMPONENTS AND CLADDING AS 49PSF
 INTERIOR, 40PSF EDGE.SAME NUMBER FOR
 POSITIVE AND NEGATIVE?SEE ASCE7-98,
 FBC CHAPTER 16; USUALLY THE EDGES ARE
 SUBJECT TO GREATER PRESSURE THAN THE
 INTERIOR.PLEASE CLARIFY.
  
 9.)FOR THE MODIFIED ROOF PRODUCT
 APPROVAL, PLEASE REMOVE SHEETS WHICH DO
 NOT APPLY TO THIS JOB SO THAT CODE
 COMPLIANCE CAN BE DETERMINED.PLEASE
 KEEP SHEETS 1-6, 35-36.ALSO INCLUDE
 THE ONE TWO SHEETS OF WHICHEVER APPROVED
 ASSEMBLY (FROM SHEETS 7 THROUGH 34) THAT
 YOU ARE USING.PLEASE NOTE THAT IF THE
 ASSEMBLY REFERS TO PRODUCT LIMITATION
 #9, ENHANCED FASTENING FOR CORNER ZONES
 CANNOT BE USED.
  
 10.) IT IS NOT CLEAR IF THE ACCESSIBLE
 ROUTE IS COMPLIANT.AT THE ACCESSIBLE
 ENTRANCE FOR THE OFFICE, GRADING &
 DRAINAGE PLAN, ELEVATIONS FOR THE
 SIDEWALK ARE GIVEN, 22.25 AND 21.75.
 THEY APPEAR TO BE APPROXIMATELY 8? APART
 (IS THE DISTANCE GREATER?), GIVING A
 SLOPE OF 1:16 (5.2%).THEREFORE WOULD
 NEED TO SHOW COMPLIANCE AS A RAMP
 (GREATER THAN 1:20, 5%).PLEASE
 CLARIFY ACTUAL SLOPE. NOTE - CLARIFIED
 WITH ENGINEER, RAMP INDICATED ON PLAN -
 OKAY SMH
  
 11.) THE SEAL REQUIRES A DATE,
 FAC61G1-15 (ARCHITECTURAL SHEETS).
  
 12.)MONUMENT SIGN, A201 HAS INCORRECT
 ADDRESS.ALSO, THE SIGN REQUIRES A
 SEPARATE PERMIT.IT IS NOT NECESSARY TO
 REMOVE THE DETAIL FROM THE PLAN.
  
 13.)THE ROOF DESIGN PRESSURE IS 61,
 SKYLIGHT PRODUCT APPROVAL HAS A
 LIMITATION OF +52.5/-56.1.
  
 14.) THE SCALE ON A700 FOR THE SERVICE
 GARAGE SHOWS THE GARAGE AS APPROXIMATELY
 90? DEEP, REQUIRING TWO MEANS OF EGRESS.
 THIS DIMENSION IS NOT CONSISTENT WITH
 THE STRUCTURALS.PLEASE ADDRESS.
  
 15.) SUBMIT A PERMIT APPLICATION FOR THE
 GARAGE.THE PACKAGE CAN REMAIN ONE
 PACKAGE BUT TWO PERMIT NUMBERS MUST BE
 ASSIGNED.