Plan Review Notes
Plan Review Notes For Permit 05011539
Permit Number 05011539
Review Stop P
Sequence Number 1
Notes
Date Text
2005-03-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FBC-2001 BUILDING
 CITY WPB CODE
  
 1) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE. SECTION 608.13.2.
 2) SEPARATE PERMIT/PLANS REQUIRED FOR
 THE IRRIGATION. SECTION 104.3.1.1.
 3) SHT A-503 INDICATE WIDTH (30") AND
 KNEE CLEARANCE (27") ON DETAIL. SECTION
 11-4.24.3. CLEAR FLOOR SPACE 11-4.24.5
 (FORWARD APPROACH REQUIRED), EXPOSED
 PIPES AND SURFACES 11-4.24.6, & FAUCETS
 11-4.24.7.
 4) SHT A402 SUBMIT A DETAIL FOR MEN'S
 AND WOMEN'S TOILET ROOMS SHOWING
 COMPLIANCE WITH THE FOLLOWING.
 A) CLEAR FLOOR SPACE 11-4.16.2
 B) HEIGHT 11-4.16.3
 C) GRAB BARS 11-4.16.4
 D) HEIGHT 11-4.18.2
 E) CLEAR FLOOR SPACE 11-4.18.3
 F) FLUSH CONTROLS 11-4.18.4
 G) CLEAR FLOOR SPACE 11-4.19.3
 H) FAUCETS 11-4.19.7
 I) 5 FT. TURNING AREA IN TOILET ROOMS
 11-4.22.3.
 5) SUBMIT A DETAIL FOR THE DRINKING
 FOUNTAIN SHOWING COMPLIANCE WITH:
 A) SPOUT HEIGHT 11-4.15.2
 B) CLEAR FLOOR SPACE 11-4.15.5
 6) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR THE SIZING OF THE
 OIL/WATER SEPARATOR. WASTE ORD #2938-96.
 (561) 837-4074 - E-MAIL [email protected].
 7) SHT P-101 WATER HEATER DETAIL,
 DIELECTRIC UNIONS ARE NOT APPROVED.
 DELETE FROM DETAIL OR CHANGE TO
 DIELECTRIC COUPLINGS.
 8) SHT P-102 INDICATE THE TYPE OF
 MATERIAL USED IN THE COMPRESSED AIR
 SYSTEM. SECTION 104.2.1.
 9) SHT P601 SANT. RISER DIAGRAM, FIXTURE
 F6B (ICE MAKER) SHALL DRAIN TO AN
 INDIRECT WASTE RECEPTOR. SECTION 802.
 10) SHT P-601 SERVICE GARAGE SANT. RISER
 DIAGRAM, HORIZONTAL DRY VENT DOWSTREAM
 FROM FIXTURE F1A (W/C) NOT APPROVED.
 SECTIONS 905.3/905.4.
 11) SHT P-601 WATER RISER DIAGRAM, WATER
 HAMMER ARRESTOR IS REQUIRED AT THE ICE
 MAKER PER SECTION 604.9. WATER HAMMER
 ARRESTOR SHALL BE LOCATED NEAR THE
 FIXTURE IN AN "EFFECTIVE RANGE" NOT IN
 THE CEILING. PDI-WH 201.
 12) SHT P-601 WATER RISER DIAGRAM, THE
 VALVES REQUIRED BY SECTION 606.1(4),
 WATER DOWN-FEED LINES, SHALL BE SHOWN ON
 THE ISOMETRIC. SECTION 104.2.1.
 13) SUBMIT A PLUMBING LEGEND INDICATING
 ALL FIXTURE, AND WATER HAMMER
 DESIGNATIONS. SECTION 104.2.1.
 13) SHT M-101 HVAC ROOF PLAN, CONDENSATE
 SHALL NOT DRAIN INTO THE SANT. SYSTEM.
 CONDENSATE SHALL DRAIN SEPARATELY INTO A
 CATCH BASIN, DRYWELL, OR STORM DRAIN
 LINE IF DRAINING TO STORM SEWER. CITY
 CODE SECTION 90-125(5)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692