| 2005-03-04 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | FBC-2001 BUILDING |
| | CITY WPB CODE |
| | |
| | 1) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. SECTION 608.13.2. |
| | 2) SEPARATE PERMIT/PLANS REQUIRED FOR |
| | THE IRRIGATION. SECTION 104.3.1.1. |
| | 3) SHT A-503 INDICATE WIDTH (30") AND |
| | KNEE CLEARANCE (27") ON DETAIL. SECTION |
| | 11-4.24.3. CLEAR FLOOR SPACE 11-4.24.5 |
| | (FORWARD APPROACH REQUIRED), EXPOSED |
| | PIPES AND SURFACES 11-4.24.6, & FAUCETS |
| | 11-4.24.7. |
| | 4) SHT A402 SUBMIT A DETAIL FOR MEN'S |
| | AND WOMEN'S TOILET ROOMS SHOWING |
| | COMPLIANCE WITH THE FOLLOWING. |
| | A) CLEAR FLOOR SPACE 11-4.16.2 |
| | B) HEIGHT 11-4.16.3 |
| | C) GRAB BARS 11-4.16.4 |
| | D) HEIGHT 11-4.18.2 |
| | E) CLEAR FLOOR SPACE 11-4.18.3 |
| | F) FLUSH CONTROLS 11-4.18.4 |
| | G) CLEAR FLOOR SPACE 11-4.19.3 |
| | H) FAUCETS 11-4.19.7 |
| | I) 5 FT. TURNING AREA IN TOILET ROOMS |
| | 11-4.22.3. |
| | 5) SUBMIT A DETAIL FOR THE DRINKING |
| | FOUNTAIN SHOWING COMPLIANCE WITH: |
| | A) SPOUT HEIGHT 11-4.15.2 |
| | B) CLEAR FLOOR SPACE 11-4.15.5 |
| | 6) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE FOR THE SIZING OF THE |
| | OIL/WATER SEPARATOR. WASTE ORD #2938-96. |
| | (561) 837-4074 - E-MAIL [email protected]. |
| | 7) SHT P-101 WATER HEATER DETAIL, |
| | DIELECTRIC UNIONS ARE NOT APPROVED. |
| | DELETE FROM DETAIL OR CHANGE TO |
| | DIELECTRIC COUPLINGS. |
| | 8) SHT P-102 INDICATE THE TYPE OF |
| | MATERIAL USED IN THE COMPRESSED AIR |
| | SYSTEM. SECTION 104.2.1. |
| | 9) SHT P601 SANT. RISER DIAGRAM, FIXTURE |
| | F6B (ICE MAKER) SHALL DRAIN TO AN |
| | INDIRECT WASTE RECEPTOR. SECTION 802. |
| | 10) SHT P-601 SERVICE GARAGE SANT. RISER |
| | DIAGRAM, HORIZONTAL DRY VENT DOWSTREAM |
| | FROM FIXTURE F1A (W/C) NOT APPROVED. |
| | SECTIONS 905.3/905.4. |
| | 11) SHT P-601 WATER RISER DIAGRAM, WATER |
| | HAMMER ARRESTOR IS REQUIRED AT THE ICE |
| | MAKER PER SECTION 604.9. WATER HAMMER |
| | ARRESTOR SHALL BE LOCATED NEAR THE |
| | FIXTURE IN AN "EFFECTIVE RANGE" NOT IN |
| | THE CEILING. PDI-WH 201. |
| | 12) SHT P-601 WATER RISER DIAGRAM, THE |
| | VALVES REQUIRED BY SECTION 606.1(4), |
| | WATER DOWN-FEED LINES, SHALL BE SHOWN ON |
| | THE ISOMETRIC. SECTION 104.2.1. |
| | 13) SUBMIT A PLUMBING LEGEND INDICATING |
| | ALL FIXTURE, AND WATER HAMMER |
| | DESIGNATIONS. SECTION 104.2.1. |
| | 13) SHT M-101 HVAC ROOF PLAN, CONDENSATE |
| | SHALL NOT DRAIN INTO THE SANT. SYSTEM. |
| | CONDENSATE SHALL DRAIN SEPARATELY INTO A |
| | CATCH BASIN, DRYWELL, OR STORM DRAIN |
| | LINE IF DRAINING TO STORM SEWER. CITY |
| | CODE SECTION 90-125(5) |
| | |