| Plan Review Notes For Permit 05011539 |
| Permit Number |
05011539 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-03-08 00:00:00 | DENIED: | | | 1.NO COMBUSTIBLES ALLOWED ABOVE THE | | | CEILING IN THE RETURN AIR PLENUM PER | | | 2001 FBC/M 602.2.1. | | | | | | 2.PLEASE PROVIDE OUTSIDE AIR | | | CALCULATIONS PER 2001 FBC(M) TABLE | | | 403.3.INDICATE ALL AREAS, SERVICE | | | GARAGE, OFFICE, ETC. | | | | | | 3.PLAN SHEET M-001 SPECIFICATION 15001 | | | E.INDICATES HEIGHT REQUIREMENT FOR | | | STANDS.PLEASE NOTE THE REQUIREMENT | | | DOES NOT INDICATE THAT THE HEIGHT | | | REQUIREMENT IS FROM THE ROOF SURFACE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|