Plan Review Notes
Plan Review Notes For Permit 05011539
Permit Number 05011539
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-03-10 00:00:001. WET FIRE HYDRANTS ARE REQUIRED
 PRIOR TO, DURING, AND AFTER
 CONSTRUCTION.
  
 2. SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION.
  
 3. ELECTRONIC SWITCHES, CHAIN AND LOCKS
 WILL BE REQUIRED ON THE BACKFLOW
 DEVICE.
  
 4. CONSTRUCTION, DEMOLITION, AND
 RENOVATION TO COMPLY WITH NFPA 241.
  
 5. SEPARATE PLANS AND PERMITS
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER SYSTEM.
  
 6. KNOX-BOXES WILL BE REQUIRED FOR
 THE SITE.
  
 7. BUILDING ADDRESS REQUIRED ON THE
 BUILDING. 6" HIGH LETTERS REQUIRED.
  
 8. PLEASE PROVIDE DETAILS ON SECURITY
 DOOR LOCKS ON PAGE E-501.
  
 9. SOME DIRECTIONAL ARROWS ON AT LEAST
 TWO EXIT SIGNS ARE DIRECTING PERSONS
 INTO THE WAREHOUSE AREA.
  
 10. WHAT HAPPENS WHEN LOSS OF POWER
 OCCURS TO THE ELECTRONIC GATES. WHAT
 PROVISIONS HAVE BEEN MADE FOR FIRE
 AND PARAMEDICAL EQUIPMENT WHEN LOSS
 OF POWER OCCURS. MANUAL OPERATION
 WILL BE REQUIRED IF THE GATES
 REMAIN FAIL SECURE WHEN LOSS OF
 POWER OCCURS.
  
 11. MORE DETAILS NEEDED FOR STORAGE
 RACKS.
  
 12. PLEASE INDICATE OCCUPANT LOADS
 FOR THE BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910