| 2005-02-17 00:00:00 | *********** UNSAT ********** |
| | |
| | 1)NOTE: PLEASE SEE MDP WHICH IS 277/480V |
| | IS FEEDING PANEL "RC"WHICH INDICATES |
| | 120/208V |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SEE 225.31,,32 ETC FOR |
| | MAIN DISCONNECTING MEANS REQUIRED AT |
| | DETACHED BLDG. |
| | PLEASE SEE PANEL"HC" SHOWN AS MLO. |
| | |
| | 3)NOTE: PLEASE INCLUDE AND SHOW |
| | GROUNDING AT DETACHED BLDG PER 250.32 |
| | |
| | 4)NOTE: PLEASE PROVIDE GROUNDING DETAIL |
| | FOR GROUNDING ELECTRODE SYSTEM AND FOR |
| | ALL TRANSFORMERS. PLEASE SEE |
| | 250.50,250.30 FOR REQUIRED ATTACHMENTS. |
| | PLEASE SEE FBC 104.2.1, CODE SHALL NOT |
| | BE REFERENCED IN WHOLE OR IN PART AND |
| | SHALL BE SPECIFIC. |
| | |
| | 5)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH SUBMITTED PANEL |
| | SCHEDULE. PLEASE SEE SOME MISSING. |
| | PLEASE ALSO SEE 700.12E FOR CIRCUITING |
| | OF EM/EXT LTS. |
| | THE BRANCH CIRCUIT FEEDING THE UNIT |
| | EQUIPMENT SHALL BE THE SAME BRANCH |
| | CIRCUIT AS THAT SERVING THE NORMAL |
| | LIGHTING IN THE AREA AND CONNECTED AHEAD |
| | OF ANY LOCAL SWITCHES. |
| | |
| | 6)NOTE: PLEASE PROVIDE ALL COMPLETE |
| | INFORMATION FOR FIRE PUMP, FIRE PUMP |
| | CONTROLLER. THIS IS TO INCLUDE ACTUAL |
| | SIZING OF THIS EQUIPMENT AT THIS TIME. |
| | PLEASE INCLUDE ALL MANUFACTURE SPEC/CUT |
| | SHEETS. |
| | PLEASE SHOW ALL SIZING INCLUDING LOCKED |
| | ROTOR AS REQUIRED UNDER 695.4B1 |
| | THE OVERCURRENT PROTECTIVE DEVICE(S) |
| | SHALL BE SELECTED OR SET TO CARRY |
| | INDEFINITELY THE SUM OF THE LOCKED-ROTOR |
| | CURRENT OF THE FIRE PUMP MOTOR(S) AND |
| | THE PRESSURE MAINTENANCE PUMP MOTOR(S) |
| | AND THE FULL-LOAD CURRENT OF THE |
| | ASSOCIATED FIRE PUMP ACCESSORY EQUIPMENT |
| | WHEN CONNECTED TO THIS POWER SUPPLY. |
| | PLEASE PROVIDE INFORMATION FOR |
| | DISCONNECTING MEANS PER |
| | 230.76,230.79,110.27 ETC. |
| | |
| | 7)NOTE: PLEASE PROVIDE ALL WINDING LOAD |
| | CALCULATIONS AND INFORMATION FOR BLDG |
| | REVIEW OF LIGHT POLES, INCLUDING |
| | FIXTURES. |
| | MUST MEET FBC 140 MPH. |
| | |
| | 8)NOTE: PLEASE SEE NOTE #15 ON |
| | SHEETEP101. |
| | IF THIS SYSTEM IS TO BE INCLUDED WITH |
| | THIS PERMIT PACKAGE, THEN SUBMIT ALL |
| | SPECS FOR DEVICES TO BE USED AND SUBMIT |
| | INFORMATION FOR EGRESS/ FAIL SAFE |
| | OPERATION ETC. PLEASE SEE FIRE REVIEW |
| | FOR THIS REQUIRED INFORMATION. |
| | |
| | PLEASE SEE MANY OF THE ABOVE ITEMS AND |
| | LOCATIONS OF THESE ITEMS ARE |
| | REDLINED/HIGH-LIGHTED ON ONE SET OF |
| | PLANS. |
| | |
| | PLEASE BE SURE TO SEE POSSIBLE COMMENTS |
| | FROM OTHER REVIEWER(S) WHICH MAY AFFECT |
| | ELECTRICAL PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW . IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |