Plan Review Notes
Plan Review Notes For Permit 05011539
Permit Number 05011539
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-17 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SEE MDP WHICH IS 277/480V
 IS FEEDING PANEL "RC"WHICH INDICATES
 120/208V
 215.5
  
 2)NOTE: PLEASE SEE 225.31,,32 ETC FOR
 MAIN DISCONNECTING MEANS REQUIRED AT
 DETACHED BLDG.
 PLEASE SEE PANEL"HC" SHOWN AS MLO.
  
 3)NOTE: PLEASE INCLUDE AND SHOW
 GROUNDING AT DETACHED BLDG PER 250.32
  
 4)NOTE: PLEASE PROVIDE GROUNDING DETAIL
 FOR GROUNDING ELECTRODE SYSTEM AND FOR
 ALL TRANSFORMERS. PLEASE SEE
 250.50,250.30 FOR REQUIRED ATTACHMENTS.
 PLEASE SEE FBC 104.2.1, CODE SHALL NOT
 BE REFERENCED IN WHOLE OR IN PART AND
 SHALL BE SPECIFIC.
  
 5)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED PANEL
 SCHEDULE. PLEASE SEE SOME MISSING.
 PLEASE ALSO SEE 700.12E FOR CIRCUITING
 OF EM/EXT LTS.
 THE BRANCH CIRCUIT FEEDING THE UNIT
 EQUIPMENT SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL
 LIGHTING IN THE AREA AND CONNECTED AHEAD
 OF ANY LOCAL SWITCHES.
  
 6)NOTE: PLEASE PROVIDE ALL COMPLETE
 INFORMATION FOR FIRE PUMP, FIRE PUMP
 CONTROLLER. THIS IS TO INCLUDE ACTUAL
 SIZING OF THIS EQUIPMENT AT THIS TIME.
 PLEASE INCLUDE ALL MANUFACTURE SPEC/CUT
 SHEETS.
 PLEASE SHOW ALL SIZING INCLUDING LOCKED
 ROTOR AS REQUIRED UNDER 695.4B1
 THE OVERCURRENT PROTECTIVE DEVICE(S)
 SHALL BE SELECTED OR SET TO CARRY
 INDEFINITELY THE SUM OF THE LOCKED-ROTOR
 CURRENT OF THE FIRE PUMP MOTOR(S) AND
 THE PRESSURE MAINTENANCE PUMP MOTOR(S)
 AND THE FULL-LOAD CURRENT OF THE
 ASSOCIATED FIRE PUMP ACCESSORY EQUIPMENT
 WHEN CONNECTED TO THIS POWER SUPPLY.
 PLEASE PROVIDE INFORMATION FOR
 DISCONNECTING MEANS PER
 230.76,230.79,110.27 ETC.
  
 7)NOTE: PLEASE PROVIDE ALL WINDING LOAD
 CALCULATIONS AND INFORMATION FOR BLDG
 REVIEW OF LIGHT POLES, INCLUDING
 FIXTURES.
 MUST MEET FBC 140 MPH.
  
 8)NOTE: PLEASE SEE NOTE #15 ON
 SHEETEP101.
 IF THIS SYSTEM IS TO BE INCLUDED WITH
 THIS PERMIT PACKAGE, THEN SUBMIT ALL
 SPECS FOR DEVICES TO BE USED AND SUBMIT
 INFORMATION FOR EGRESS/ FAIL SAFE
 OPERATION ETC. PLEASE SEE FIRE REVIEW
 FOR THIS REQUIRED INFORMATION.
  
 PLEASE SEE MANY OF THE ABOVE ITEMS AND
 LOCATIONS OF THESE ITEMS ARE
 REDLINED/HIGH-LIGHTED ON ONE SET OF
 PLANS.
  
 PLEASE BE SURE TO SEE POSSIBLE COMMENTS
 FROM OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW . IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
  