| 2005-02-14 00:00:00 | PERMIT #05011539 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | |
| | 1. THE ADDRESS ON THE APPLICATION |
| | CONFLICTS WITH THE ADDRESS IN OUR |
| | RECORDS (5163 TYLERLAKES BOULEVARD).IF |
| | THERE ARE ANY QUESTIONS REGARDING |
| | ADDRESSING, PLEASE CONTACT JOHN HIGGINS, |
| | 561-822-1239. |
| | |
| | 2. A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3. IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.561-233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 4. PROVIDE AN ORIGINAL SOILS |
| | INVESTIGATION REPORT (PHOTOCOPY |
| | PROVIDED), SIGNED AND SEALED AS PER |
| | FAC61G15-23.002. |
| | |
| | 5. FBC*105.3, INSPECTION SERVICES.THE |
| | BUILDING OFFICIAL MAY MAKE, OR CAUSE TO |
| | BE MADE BY OTHERS, THE INSPECTIONS |
| | REQUIRED BY SECTION 105, IN ACCORDANCE |
| | WITH PART XII OF CHAPTER 468, FLORIDA |
| | STATUTES.HE/SHE MAY ACCEPT REPORTS OF |
| | INSPECTORS OF RECOGNIZED INSPECTION |
| | SERVICES, PROVIDED THAT AFTER |
| | INVESTIGATION HE/SHE IS SATISFIED AS TO |
| | THEIR QUALIFICATIONS AND RELIABILITY.A |
| | CERTIFICATE CALLED FOR BY ANY PROVISION |
| | OF THE TECHNICAL CODES SHALL NOT BE |
| | BASED ON SUCH REPORTS UNLESS THE SAME |
| | ARE IN WRITING AND CERTIFIED BY A |
| | RESPONSIBLE OFFICER OF SUCH SERVICE. |
| | THE BUILDING OFFICIAL MAY REQUIRE THE |
| | OWNER TO EMPLOY AN INSPECTION SERVICE IN |
| | THE FOLLOWING INSTANCES SHOULD THE |
| | BUILDING SIZE, STYLE OR DESIGN DEMAND |
| | DETAILED, LENGTHY OR CONSTANT |
| | INSPECTIONS BEYOND THE NORMAL SCHEDULING |
| | ALLOWANCES FOR INSPECTIONS BY CITY |
| | STAFF: |
| | |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I |
| | OR TYPE II CONSTRUCTION; |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS; |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON |
| | COMPRESSIVE STRENGTH (F?C) IN EXCESS OF |
| | 3000 PSI; |
| | 4. FOR PILE DRIVING; |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN |
| | 20,000 SQUARE FOOT; |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN |
| | HEIGHT; |
| | 7. FOR BUILDINGS AND STRUCTURES OF |
| | UNUSUAL DESIGN OR METHODS OF |
| | CONSTRUCTION. |
| | |
| | PLEASE SEE THE CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE |
| | AND CONTACT HAROLD PISKURA, INSPECTION |
| | SERVICES MANAGER/ABO, 561-805-6711. |
| | |
| | 6. PROVIDE A TITLE BLOCK FOR THE SEALED |
| | STRUCTURAL CALCS, FAC61G15-23.002. |
| | |
| | 7. PROVIDE A SURVEY FOR THIS PROPERTY. |
| | |
| | 8. THE NUMBER OF ACCESSIBLE PARKING |
| | SPACES IS TO COMPLY WITH |
| | FBC11-4.1.2(5)(A) (SITE PLAN). |
| | |
| | 9. THE STRIPING FOR THE ACCESSIBLE |
| | PARKING SPACE DETAIL (TYPICAL PARKING |
| | STALLS, SITE PLAN) IS TO COMPLY WITH THE |
| | CITY OF WEST PALM BEACH STANDARD, SEE |
| | ATTACHED.PLEASE NOTE THAT THE STRIPING |
| | APPEARS CORRECT GRAPHICALLY BUT THE |
| | DIMENSION (12IN.) IS INCORRECT (SHOULD |
| | BE 16IN). |
| | |
| | 10. CERTIFICATE OF AUTHORIZATION NUMBER |
| | IS TO BE ON THE TITLE BLOCK FOR THE |
| | HASKELL COMPANY, FAC61G1-16.003, 004. |
| | |
| | 11. SEPARATE PERMIT REQUIRED FOR THE |
| | SERVICE GARAGE. |
| | |
| | 12. THE SQUARE FOOT TOTALS ON THE SITE |
| | PLAN, SHEET A-100, AND THE ENERGY CALC |
| | ARE NOT CONSISTENT. |
| | |
| | 13. SHEET A100, MEANS OF EGRESS, REFERS |
| | TO THE UBC.ALL REFERENCES ARE TO CITE |
| | GOVERNING CODE, FBC2001.PLEASE REVISE; |
| | ALSO AN ADDITIONAL OCCUPANCY |
| | CLASSIFICATION OF ASSEMBLY HAS BEEN |
| | ADDED THERE WHICH DOES NOT APPEAR IN THE |
| | OCCUPANCY SECTION.THE 15/SF DOES NOT |
| | COMPLY WITH FBC REQUIREMENTS FOR |
| | ASSEMBLY. |
| | |
| | 14. SHEET A100, OCCUPANCY AND MEANS OF |
| | EGRESS, DECLARES STORAGE OCCUPANCY FOR |
| | THE WAREHOUSE, FBC312.IT APPEARS THAT |
| | WITH 225 PEOPLE PER SHIFT, THE PRINCIPAL |
| | USE IS NOT STORAGE.PLEASE CLARIFY. |
| | |
| | 15. SHEET A100, OCCUPANCY AND MEANS OF |
| | EGRESS, DECLARES STORAGE OCCUPANCY FOR |
| | THE VEHICLE MAINTENANCE BUILDING, |
| | FBC312.PLEASE SEE FBC305. |
| | |
| | 16. S110, STRUCTURAL NOTE J2 REFERS TO |
| | NEVADA; PLEASE REVISE TO FLORIDA. |
| | |
| | 17. S110, STRUCTURAL NOTE K, REFERS TO |
| | UBC1701; PLEASE REVISE. |
| | |
| | 18. PROVIDE THE MANEUVERING CLEARANCE |
| | FOR DOOR 119A, 127A, 127B, SHEET A-401, |
| | FBC CHAPTER 11 FIGURE 25. |
| | |
| | 19. THE STAIR RAILS ALSO SERVE AS A |
| | GUARDRAIL AND ARE TO COMPLY WITH FBC1015 |
| | (OVER 30? ABOVE GROUND), SHEET A502 AND |
| | ANY OTHER APPLICABLE DETAILS. |
| | |
| | 20. PROVIDE DESIGN CRITERIA FOR THE |
| | HANDRAIL AND GUARDRAIL, A502, |
| | FBC1608.2.1 AND FBC1608.2.2 |
| | RESPECTIVELY. |
| | |
| | 21. PROVIDE A DETAIL FOR THE RAMP |
| | HANDRAIL AND GUARDRAIL. |
| | |
| | 22. SHOW COMPLIANCE WITH FBC11-4.3.2, |
| | ACCESSIBLE ROUTE.IT APPEARS THAT THE |
| | CROSS SLOPE FOR THE SIDEWALK (GRADING & |
| | DRAINAGE PLAN) EXCEEDS THE 1:50 ALLOWED |
| | BY FBC11-4.3.7. |
| | |
| | 23. PROVIDE THE INFORMATION REQUIRED BY |
| | FBC1606.1.7.NOTE THAT DESIGN PRESSURES |
| | FOR COMPONENTS AND CLADDING WERE NOT |
| | PROVIDED. |
| | |
| | 24. THE VP STEEL STRUCTURALS (SHEET 8 |
| | FOR VEHICLE MAINTENANCE BUILDING, SHEET |
| | 23 FOR OFFICE/WAREHOUSE) SPECIFY A |
| | DESIGN PRESSURE OF 285PSF FOR ZONE 3. |
| | THIS EXCEEDS THE DESIGN PRESSURE OF THE |
| | ROOFING PRODUCT APPROVALS SUBMITTED. |
| | ADDRESS. |
| | |
| | 25. ORIGINAL SIGNATURE AND DATE REQUIRED |
| | (VP STEEL STRUCTURALS).PHOTOCOPIES OF |
| | A SIGNATURE NOT ACCEPTABLE PER FBPE. |
| | ALSO SOME SHEETS WEREN?T SIGNED AND |
| | DATED; OTHERS WERE NOT SIGNED, SEALED |
| | AND DATED.ALL DOCUMENTS SUBMITTED BY |
| | AN ENGINEER FOR PUBLIC RECORD ARE TO |
| | BEAR AN ORIGINAL SEAL, SIGNATURE AND |
| | DATED FAC61G15-23.002. |
| | |
| | 26. EACH SHEET IS TO HAVE A TITLE BLOCK |
| | WITH THE INFORMATION REQUIRED BY |
| | FAC61G15-23.002 (VP STEEL STRUCTURALS). |
| | |
| | 27. FOR PRODUCT APPROVALS FL3600.4 AND |
| | FL3612.8 SUBMITTED, PROVIDE A COPY OF |
| | THE TEST REPORT AND INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 28. INDICATE ON FL3612.8 WHICH PRODUCT |
| | YOU ARE INSTALLING.WINDOWS AND DOORS |
| | WHICH ARE NOT IMPACT REQUIRE IMPACT |
| | PROTECTION FBC1606.1.4. |