| Plan Review Notes For Permit 05011534 |
| Permit Number |
05011534 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-07 00:00:00 | | | | | | | THE TYPE OF POOL HEATER HAS BEEN CHANGED | | | FROM GAS TO ELECTRIC, THIS REQUIRES A | | | LOAD CALCULATION FROM THE ENGINEER. ALSO | | | SPECIFICATIONS FOR THE EQUIPMENT BEING | | | INSTALLED MUST BE SUBMITTED FOR REVIEW. | | | | | | THE SCHEMATIC INDICATES A GAS HEATER, | | | PLEASE CHANGE DRAWING TO CORRELATE WITH | | | THE SCOPE OF WORK. | | | | | | THE ENGINEER OBVIOUSLY WAS NOT AWARE OF | | | THESE CHANGES. PLEASE SEND THE PLAN BACK | | | TO MR. RICE FOR HIS APPROVAL. NOTE | | | CHANGES TO SEALED PLANS CAN ONLY BE MADE | | | BY THE ENGINEER OF RECORD PER 471.025 | | | FS. | | | | | | AN ELECTRICAL PERMIT IS REQUIRED FOR | | | THIS WORK. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|