| 2005-03-07 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)DECLARE AN OCCUPANCY, FBC CHAPTER | | | 3. | | | | | | 2.)SEE PREVIOUS COMMENTS 3, 4, 5. | | | EITHER NOT ADDRESSED OR NOT ADDRESSED | | | PROPERLY. | | | | | | 3.)BOTTOM DISTANCE OF RAIL TO SLAB IS | | | SHOWN AS 3", NOT COMPLIANT WITH | | | FBC1015.3. (REJECT A 2" OBJECT). | | | | | | 4.)SEE ATTACHED FS553.80(2)(B). |
|