| Plan Review Notes For Permit 05011510 |
| Permit Number |
05011510 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-11 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | SHEET E-1 INDICATES A 40KW GENERATOR AND | | | E-2 INDICATES 100KW, PLEASE CORRELATE. | | | | | | SUPPLY MFGR SPECIFICATION FOR THE | | | GENERATOR. | | | | | | GIVE SPECIFICATIONS FOR PANEL "A"(AMPS, | | | VOLTS RATING, MAIN BKR.OR MLO)ETC. | | | | | | THE VALUE ON THE APPLICATION MUST | | | REFLECT THE COST OF ALL MATERIAL AND | | | LABOR IN THE SCOPE OF WORK TO BE DONE. | | | THIS INCLUDES THE GENERATOR AND RELATED | | | EQUIPMENT, REGARDLESS OF WHO FURNISHES | | | SAME. FBC 104.6.5. | | | | | | A GAS PERMIT IS REQUIRED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | | | | |
|