2005-02-11 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 SHEET E-1 INDICATES A 40KW GENERATOR AND
 E-2 INDICATES 100KW, PLEASE CORRELATE.
  
 SUPPLY MFGR SPECIFICATION FOR THE
 GENERATOR.
  
 GIVE SPECIFICATIONS FOR PANEL "A"(AMPS,
 VOLTS RATING, MAIN BKR.OR MLO)ETC.
  
 THE VALUE ON THE APPLICATION MUST
 REFLECT THE COST OF ALL MATERIAL AND
 LABOR IN THE SCOPE OF WORK TO BE DONE.
 THIS INCLUDES THE GENERATOR AND RELATED
 EQUIPMENT, REGARDLESS OF WHO FURNISHES
 SAME. FBC 104.6.5.
  
 A GAS PERMIT IS REQUIRED.
  