| 2005-06-28 00:00:00 | DENIED: 3RD REQUEST |
| | |
| | 1.PROVIDE DETAIL FOR THE DUCT |
| | CONNECTION TO AHU LOCATED ON THE FIRST |
| | FLOOR.PLAN SHEET A2 & M1 INDICATE A |
| | 24" X 24" R/A GRILLE.PLEASE CLARIFY |
| | DESIGN, CLOSET CANNOT BE USED AS A |
| | RETURN AIR PLENUM WITH THE DOOR OPENINGS |
| | INTO THE GARAGE (CARBON MONOXIDE).2001 |
| | FBC(M) 603.9 & 602. |
| | |
| | 2.PLEASE NOTE RETURN AIR JUMPERS |
| | SHALL BE SIZED IN ACCORDANCE WITH 2001 |
| | FBC(M)601.4 EXCEPTION #1 & 3.THE |
| | SECOND FLOOR SPARE BEDROOMS SHALL BE A |
| | MINIMUM OF 12" AND THE MASTER SUITE |
| | SHALL BE A MINIMUM OF 14".PLEASE |
| | REVISE. |
| | |
| | 3.PLAN SHEET M2 INDICATES RETURN AIR |
| | BACK TO THE AHU THROUGH A LOUVERED DOOR. |
| | THE DOOR SCHEDULE ON PLAN SHEET A3, DOOR |
| | #5TO THE AHU-2 CLOSET INDICATES A |
| | SOLID CORE DOOR.PLEASE REVISE. |
| | |
| | 4.PROVIDE AN EQUIPMENT SCHEUDLE AS |
| | DICTATED BY THE ENERGY CALCULATIONS. |
| | |
| | PLEASE NOTE, THE FLOOR PLAN IN THE |
| | GARAGE AREA ON PLAN SHEET E1 DOES NOT |
| | CORRELATE WITH A2 & M1 WITH RESPECT TO |
| | LOCATION OF THE AHU & 80 GAL EWH. |
| | PLEASE CLARIFY. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE |
| | CONTACT PATTY KRAUSS AT (561)805-6719. |