| 2005-06-03 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | |
| | 1- PROVIDE STRUCTURAL BUCK DETAILS FOR |
| | SWING DOOR AT GARAGE. SEE PRODUCT |
| | APPROVAL FOR SIZE REQUIRED. |
| | **NOTE: IT'S THE DESIGNER OF RECORD THE |
| | ONE WHO PROVIDES THIS INFORMATION NOT |
| | THE PRODUCT APPROVAL. SECTION 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001 AND SECTION |
| | 1707.4.4.2 FBC 2001. |
| | |
| | 2- SECTION 1/A6 IS INCOMPLETE. IS |
| | MISSING 2ND FLOOR FRAMING ON THE OTHER |
| | SIDE OF THE WALL. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 3- A) PROVIDE UPLIFT CALCULATIONS FOR |
| | ROOF TRUSSES TO CLARIFYWHY UPLIFT |
| | CALCULATIONS SHOWN ON PLANS ARE THE SAME |
| | FOR THE FIRST STORY ROOF AS THE ONES FOR |
| | THE SECOND STORY ROOF. SECTION 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |
| | |
| | B) CLARIFY WHY USING CONNECTORS ON |
| | SECOND FLOOR ROOF THAT DON'T PROVIDE |
| | RESISTANCE FOR LATERAL LOADS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | C) CLARIFY WHY USING STRONGER CONNECTORS |
| | FOR ROOF AT FIRST FLOOR THAN AT SECOND |
| | FLOOR ROOF. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 4- SHEET A6: UNABLE TO FIND SIMPSON |
| | LUSC212 AND LUS212 CONNECTORS IN THE |
| | SIMPSON CATALOGUE. WHERE WERE THEY TAKEN |
| | FROM? PROVIDE COMPLETE CONNECTOR |
| | INFORMATION AND PRODUCT APPROVAL. SEC. |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 5- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: A) USP CONNECTORS |
| | SPECIFIED ON PLANS. |
| | |
| | B) GARAGE DOORS. DRAWINGS SUBMITTED ARE |
| | NOT LEGIBLE. |
| | |
| | 6-A) ON FIRST SUBMITTAL PACKAGE THERE |
| | WAS A PRODUCT APPROVAL FOR RAILING |
| | SYSTEM TO BE USED IN THE HOUSE. IT WAS |
| | NOT GOOD BECAUSE IT WAS TO BE ANCHORED |
| | TO CONCRETE SLAB. NOW, THERE IS NO |
| | SUBMITTAL FOR RAILINGS NOW. |
| | PROVIDE COMPLETE SPECS AND DETAILS FOR |
| | CONSTRUCTION OF RAILING SYSTEMS. SPECIFY |
| | ALL CONNECTORS, ETC. DESIGN TO COMPLY |
| | WITH SEC. 1608.2 FBC 2001. |
| | |
| | B) TYPICAL STAIR DETAIL ON SHEET A10 |
| | DOESN'T MATCH STAIRS SHOWN ON PLANS. |
| | LOOK AT FIRST AND LAST STEP. ALSO, NEED |
| | TO SPECIFY ALL FRAMING CONNECTORS FOR |
| | POSTS ETC. |
| | AND, REVISE CONNECTOR TO BE ATTACHED TO |
| | MASONRY. NEED TO SPECIFY MASONRY |
| | CONNECTOR. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 7- SECTIONS SHOWN ON SHEET A11 DON'T |
| | APPLY TO THIS PROJECT. PROVIDE SECTIONS |
| | THAT APPLY. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ AT (561)805-6712. |