| 2005-02-14 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SHT SP1 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. | | | A) FIRST FLOOR BATHROOMS SHOW TUBS ON | | | THE FLOOR PLAN, BUT SHOW SHOWERS ON THE | | | SANT. RISER DIAGRAM. SECTION 104.2.1. | | | B) ALL SHOWERS, TUBS, BIDET, & WASH | | | MACHINE REQUIRE A TRAP. SECTION 901.2.1. | | | C) STANDPIPE FOR THE WASH MACHINE SHALL | | | BE UPSTREAM OF THE TRAP. PLEASE SHOW ON | | | THE RISER DIAGRAM. SECTION 104.2.1. | | | | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|