| 2005-02-18 00:00:00 | BUILDING REVIEW CHECKLIST: |
| | 1- WHEN APPLYING FOR BUILDING PERMIT, |
| | PLEASE PAY IMPACT FEES AND BRING BACK |
| | STAMPED DRAWINGS AND PAID RECEIPT. |
| | ALSO, PROVIDE COPY OF RECORDED NOTICE OF |
| | COMMENCEMENT. |
| | |
| | 2- CLARIFY IF USING IMPACT GLAZING OR |
| | STORM SHUTTERS. BOTH PACKAGES WERE |
| | SUBMITTED. IF USING STORM SHUTTERS, |
| | THEN, PROVIDE COMPLETE INFORMATION. |
| | |
| | 3- REVISE HANDRAIL HEIGHT SHOWN ON STAIR |
| | DETAIL. SHEET A10. HANDRAIL NEED TO BE |
| | BETWEEN 34" AND 38" (NOT 42"). SECTION |
| | 1007.5.1 FBC 2001 EXCEPTION #3. |
| | **NOTE: GUARDRAIL AND HANDRAIL ARE NOT |
| | THE SAME. |
| | |
| | 4-SPECIFY ROOF TILE FASTENING AS REQ'D |
| | BY SEC. 104.2.1.1 CITY AMENDMENTS TO FBC |
| | |
| | 5- GARAGE DOOR SIZE SPECIFIED ON DOOR |
| | SCHEDULE IS NOT THE SAME AS SHOWN ON |
| | ELEVATIONS. REVISE AS REQUIRED. |
| | |
| | 6- PROVIDE SURVEY WITH LAYOUT THAT |
| | MATCHES PLANS SUBMITTED. |
| | |
| | 7- OWNER/AGENT NEEDS TO SIGN AND DATE |
| | THE ENERGY CALCULATIONS FORM. |
| | |
| | 8- PROVIDE SOIL TEST REPORT. |
| | |
| | 9- PROVIDE STRUCTURAL BUCK DETAILS FOR |
| | SWING AND SLIDING GLASS DOORS. (SEE |
| | PRODUCT APPROVAL FOR SIZE OF BUCK REQ'D) |
| | SECTION 104.2.1.2 SECTION 104.2.1.2 OF |
| | CITY AMENDMENTS TO FBC 2001 AND SECTION |
| | 1707.4.4.2 FBC 2001. |
| | |
| | 10- SPECIFY DRAFSTOPPING MATERIALS AND |
| | LOCATION ON 2ND FLOOR FRAMING PLAN AS |
| | REQUIRED BY SEC. 2305.2.2(1) FBC 2001. |
| | |
| | 11- PLEASE, PROVIDE ONLY THE DETAILS |
| | THAT APPLY TO THIS PROJECT TO EXPEDITE |
| | AND CLARIFY REVIEW PROCESS. |
| | |
| | 12- PROVIDE COMPLETE WALL SECTION/DETAIL |
| | AT EAST WALL SHOWING HOW ARE ROOF |
| | TRUSSES STRUCTURALLY SUPPORTED ON |
| | LEDGER. SPECIFY ALL FASTENERS. SECTION |
| | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| | |
| | 13- PROVIDE UPLIFT CALCULATIONS FOR ROOF |
| | TRUSSES(INCLUDING LATERAL FORCES) AND |
| | EXPLAIN WHY USING CONNECTORS ON 2ND |
| | FLOOR ROOF TRUSSESTHAT DON'T |
| | PROVIDE RESISTANCE TO LATERAL FORCES. |
| | (*NOTE: IT'S THE DESIGNER OF RECORD |
| | RESPONSIBILITY TO CALCULATE THE LOADS |
| | NOT THE TRUSS ENGINEER*. REVISE NOTES ON |
| | SHEETS A6 AND A7). |
| | |
| | 14- PROVIDE SMOKE DETECTOR IN FIRST FL. |
| | CLOSE TO THE STAIRS AS REQ'D BY SECTION |
| | 905.2.2 FBC 2001. |
| | |
| | 15- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: A) DOUBLE ENTRY DOORS AS |
| | SHOWN ON PLANS. |
| | B) 8'-0" HIGH SWING DOORS AS SHOWN ON |
| | PLANS (NOT 7'-0"HIGH AS SUBMITTED) |
| | C) RAILING SYSTEM TO BE INSTALLED IN |
| | FRAMED FLOORS, NOT CONCRETE SLAB. |
| | PROVIDE COMPLETE DETAILS FOR WOOD FRAMED |
| | |
| | FLOORS AS SHOWN ON PLANS. |
| | D) GARAGE DOOR INCLUDING DRAWINGS OF |
| | MODEL TO BE INSTALLED. |
| | E) FIXED WINDOWS. |
| | |
| | 16- SHEET A1: A) REVISE DETAIL F1. NEED |
| | FOOTING TO BE 12 MIN. BELOW GRADE (NOT |
| | 8"). SEC. 1804.1.3 FBC 2001. |
| | B) SPECIFY REQUIRED DEPTH BELOW GRADE |
| | ON DETAIL F3. SEC. 104.2.1.2 CITY |
| | AMENDMENTS TO FBC 2001. |
| | |
| | 17- SHEET A6: BUCKETS SPECIFIED FOR |
| | BALCONY CONSTRUCTION ARE WOOD TO WOOD |
| | JOIST HANGERS. NEED BUCKET WITH |
| | SPECIFICATIONS TO BE INSTALLED ON |
| | CONCRETE BLOCK WALL. (ALSO, WHERE ARE |
| | LUSC 212-3 CONNECTORS ON SIMPSON |
| | CATALOGUE?) |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 18- SHEET A7: SPECIFY CONNECTORS FOR |
| | HAND FRAMED HIPS AND VALLEY RAFTERS. |
| | SECTION 104.2.1.2 CITY AMENDMENTS TO FBC |
| | |
| | 19- DETAILS/SECTIONS ON SHEET A11 DON'T |
| | APPLY TO THIS PROJECT. |
| | |