| Plan Review Notes For Permit 05011482 |
| Permit Number |
05011482 |
|
| Review Stop |
M |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2006-12-27 08:49:30 | MECHANICAL REVISION | | | *** DENIED *** | | | 1) PLEASE PROVIDE COMBUSTION AIR FOR GAS CLOTHES DRYER, | | | PER 2004 FBC/R M1701.1. | | | | | | 2) RETURN AIR GRILL IN MUD ENTRY WILL NOT WORK IF THE | | | DOORS ARE CLOSED, PLEASE MOVE TO DINNING ROOM, PER 2004 | | | FBC/R M1602.4. | | | | | | 3) 9" RETURN AIR DUCT TO MASTER SUITE IS TO SMALL FOR | | | 535 CFM'S OF SUPPLY AIR, AND NEEDS TO BE 12". | | | BALANCED RETURN AIR. | | | (C)HABITABLE ROOMS ONLY SHALL BE | | | REQUIRED TO MEET THESE REQUIREMENTS FOR | | | PROPER BALANCED RETURN AIR EXCLUDING | | | BATHROOMS, CLOSETS, STORAGE ROOMS AND | | | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY | | | AIR INTO THE MASTER SUITE SHALL BE | | | INCLUDED. PER 2004 FBC/R M1602.4 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|