| 2006-02-10 00:00:00 | DENIED; | | | PLUMBING PLANS WERE NOT CORRECTED FROM | | | LAST REVIEW 11/22/05. | | | 1.TUB SHOWER AND SINK IN GARAGE ARE NOT | | | VENTED TO FBC-2001 CHAPTER 9. | | | 2.CLEANOUTS ARE REQUIRED WHEN DRAINAGE | | | SYSTEM EXITS THE HOUSE. SEE FBC-2001 | | | SEC. 708.3.5. CLEANOUTS REQUIRED AT | | | KITCHEN, TUB, SHOWER AND BATHROOM DRAIN. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|