Plan Review Notes
Plan Review Notes For Permit 05011482
Permit Number 05011482
Review Stop B
Sequence Number 2
Notes
Date Text
2005-08-05 00:00:00PERMIT #05011482
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 3.) PROVIDE A COPY OF A SURVEY FOR THIS
 PROPERTY.
  
 4.) SEE PREVIOUS LIST, ITEM #6.
 EMERGENCY EGRESS REQUIRED, FBC
 1005.4.SHOW WINDOW SIZE AND TYPE FOR
 OFFICE/GUEST BEDROOM.A NOTE WAS PLACED
 ON THE PLAN "NEW WINDOWS TO BE EGRESS".
 THIS DID NOT ADDRESS THE REQUEST FOR A
 WINDOW SIZE AND TYPE TO SHOW COMPIANCE
 WITH FBC1005.4.
  
 5.) SEE PREVIOUS LIST, ITEM #7, THE ROOF
 SHEATHING NAILING NOTE (SHEET SP)
 CONFLICTS WITH 2-A4 AND IS
 NOT COMPLIANT FOR ZONE 4, FBC*TABLE
 2306.1.SHEET SP HAS BEEN REVISED TO
 HAVE A NAILING PATTERN OF 12/6, A2 IS
 6/6 EXCEPT FOR GABLES AT 4/6.THERE ARE
 NO GABLES ON THE PLAN.THE NAILING
 SHOULD BE A MINIMUM OF 6/6 IN ZONES 1
 AND 2, 4/6 IN ZONE 3.CHECK ALL SHEETS
 AND REVISE ALL AFFECTED DETAILS AND
 NOTES TO BE COMPLIANT WITH THE MINIMUM
 REQUIREMENTS OF FBC*2306.1.
  
 6.) THE "ENERGY CALC REQUIREMENTS" FOR
 THE BLOCK WALLS ON SHEET SP DO NOT MEET
 THE MINIMUM REQUIREMENTS OF THE ENERGY
 CALCS PREPARED BY EARTHSMART.
  
 7.) IF SHUTTERS ARE TO BE A PART OF THIS
 PERMIT, COMPLETE THE SHUTTER ANCHORING
 SCHEDULE AS WELL AS A PLAN SHOWING WHICH
 OPENINGS ARE TO BE SHUTTERED AS WELL AS
 SHOWING THE MEANS OF ESCAPE FBC1005.4.5.
 NOTE THAT OCCUPANTS MUST BE ABLE TO
 ACCESS THE MEANS OF ESCAPE WITHOUT
 PASSING THROUGH A GARAGE OR A LOCKABLE
 DOOR NOT UNDER THEIR CONTROL.
  
 8.) SEE PREVIOUS LIST, ITEM #16, FLORIDA
 STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO TEST REPORTS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.PLEASE PRINT
 THE STATE PRODUCT APPROVAL, IF
 AVAILABLE, AND CLEARLY INDICATE ON THAT
 APPROVAL WHICH PRODUCT YOU ARE USING.
  
 9.)FOR THE FLAT ROOF, PLEASE CIRCLE
 THE APPROVED ASSEMBLY YOU ARE GOING TO
 INSTALL.
  
 ANY PRODUCT APPROVALS NOT SUBMITTED
 PROPERLY PRIOR TO ISSUANCE WILL REQUIRE
 SEPARATE PERMITS.
  
 10.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW FEE IS REQUIRED TO BE
 CHARGED IF THE COMMENTS ARE NOT PROPERLY
 ADDRESSED.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved