| Date |
Text |
| 2005-08-05 00:00:00 | PERMIT #05011482 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 3.) PROVIDE A COPY OF A SURVEY FOR THIS |
| | PROPERTY. |
| | |
| | 4.) SEE PREVIOUS LIST, ITEM #6. |
| | EMERGENCY EGRESS REQUIRED, FBC |
| | 1005.4.SHOW WINDOW SIZE AND TYPE FOR |
| | OFFICE/GUEST BEDROOM.A NOTE WAS PLACED |
| | ON THE PLAN "NEW WINDOWS TO BE EGRESS". |
| | THIS DID NOT ADDRESS THE REQUEST FOR A |
| | WINDOW SIZE AND TYPE TO SHOW COMPIANCE |
| | WITH FBC1005.4. |
| | |
| | 5.) SEE PREVIOUS LIST, ITEM #7, THE ROOF |
| | SHEATHING NAILING NOTE (SHEET SP) |
| | CONFLICTS WITH 2-A4 AND IS |
| | NOT COMPLIANT FOR ZONE 4, FBC*TABLE |
| | 2306.1.SHEET SP HAS BEEN REVISED TO |
| | HAVE A NAILING PATTERN OF 12/6, A2 IS |
| | 6/6 EXCEPT FOR GABLES AT 4/6.THERE ARE |
| | NO GABLES ON THE PLAN.THE NAILING |
| | SHOULD BE A MINIMUM OF 6/6 IN ZONES 1 |
| | AND 2, 4/6 IN ZONE 3.CHECK ALL SHEETS |
| | AND REVISE ALL AFFECTED DETAILS AND |
| | NOTES TO BE COMPLIANT WITH THE MINIMUM |
| | REQUIREMENTS OF FBC*2306.1. |
| | |
| | 6.) THE "ENERGY CALC REQUIREMENTS" FOR |
| | THE BLOCK WALLS ON SHEET SP DO NOT MEET |
| | THE MINIMUM REQUIREMENTS OF THE ENERGY |
| | CALCS PREPARED BY EARTHSMART. |
| | |
| | 7.) IF SHUTTERS ARE TO BE A PART OF THIS |
| | PERMIT, COMPLETE THE SHUTTER ANCHORING |
| | SCHEDULE AS WELL AS A PLAN SHOWING WHICH |
| | OPENINGS ARE TO BE SHUTTERED AS WELL AS |
| | SHOWING THE MEANS OF ESCAPE FBC1005.4.5. |
| | NOTE THAT OCCUPANTS MUST BE ABLE TO |
| | ACCESS THE MEANS OF ESCAPE WITHOUT |
| | PASSING THROUGH A GARAGE OR A LOCKABLE |
| | DOOR NOT UNDER THEIR CONTROL. |
| | |
| | 8.) SEE PREVIOUS LIST, ITEM #16, FLORIDA |
| | STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| | IN ADDITION TO TEST REPORTS, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG.PLEASE PRINT |
| | THE STATE PRODUCT APPROVAL, IF |
| | AVAILABLE, AND CLEARLY INDICATE ON THAT |
| | APPROVAL WHICH PRODUCT YOU ARE USING. |
| | |
| | 9.)FOR THE FLAT ROOF, PLEASE CIRCLE |
| | THE APPROVED ASSEMBLY YOU ARE GOING TO |
| | INSTALL. |
| | |
| | ANY PRODUCT APPROVALS NOT SUBMITTED |
| | PROPERLY PRIOR TO ISSUANCE WILL REQUIRE |
| | SEPARATE PERMITS. |
| | |
| | 10.)SEE ATTACHED FS553.80(2)(B).A 4X |
| | PLAN REVIEW FEE IS REQUIRED TO BE |
| | CHARGED IF THE COMMENTS ARE NOT PROPERLY |
| | ADDRESSED. |