| 2005-02-17 00:00:00 | DENIED; | | | 1.PAGE P-1 NOTE 20 WATER TEST ON | | | DRAINAGE PIPE IS 5' NOT 3'. | | | 2.TWO WAY CLEANOUTS ARE REQUIRED WHEN | | | DRAINAGE PIPES EXIT HOUSE. | | | 3.TUB AND SHOWER ARE NOT VENTED, | | | 4.SINK IN GARAGE REQUIRES A VENT AND | | | CANNOT BE PART OF THE WET VENT SYSTEM OF | | | A BATHROOM GROUP. SEC 909.1 | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|