2005-02-17 00:00:00DENIED;
 1.PAGE P-1 NOTE 20 WATER TEST ON
 DRAINAGE PIPE IS 5' NOT 3'.
 2.TWO WAY CLEANOUTS ARE REQUIRED WHEN
 DRAINAGE PIPES EXIT HOUSE.
 3.TUB AND SHOWER ARE NOT VENTED,
 4.SINK IN GARAGE REQUIRES A VENT AND
 CANNOT BE PART OF THE WET VENT SYSTEM OF
 A BATHROOM GROUP. SEC 909.1
 PLUMBING PLAN REVIEW BY;