| Plan Review Notes For Permit 05011482 |
| Permit Number |
05011482 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-15 00:00:00 | MECH. A/C REVIEW. | | | | | | 1. PROVIDE FL. ENERGY CALCULATIONS FOR | | | RENOVATED BULDING. FBC/CHAPTER 13 | | | /101.5.1 . | | | 2.PROVIDE FOR COMBUSTION AIR FOR GAS | | | DRYER IN LND/ROOM, TO CONFORM WITH 2001 | | | FBC/M SECTION 702 THROUGH 705 FOR SIZING | | | AND INSTALLATION.NOTE;SUBMIT GAS | | | DRYER INFORMATION FOR GAS BTU/PER HR | | | RATING. | | | 3.R/A AIR DUCTS ARE NOT SIZED. | | | 4. MAIN SUPPLY AIR DUCTS NOT SIZED. | | | 5. PROVIDE FOR R/A OUT OF BEDROOM, | | | OFFICE/GBRM. 2001 FBC/M 601.4 BALANCED | | | RETURN AIR. | | | | | | PAT RAFTER 561/805/6728 . | | | PLEASE CALL IF THEAR ENY QUESTIONS. |
|