Plan Review Notes
Plan Review Notes For Permit 05011482
Permit Number 05011482
Review Stop M
Sequence Number 1
Notes
Date Text
2005-02-15 00:00:00MECH. A/C REVIEW.
  
 1. PROVIDE FL. ENERGY CALCULATIONS FOR
 RENOVATED BULDING. FBC/CHAPTER 13
 /101.5.1 .
 2.PROVIDE FOR COMBUSTION AIR FOR GAS
 DRYER IN LND/ROOM, TO CONFORM WITH 2001
 FBC/M SECTION 702 THROUGH 705 FOR SIZING
 AND INSTALLATION.NOTE;SUBMIT GAS
 DRYER INFORMATION FOR GAS BTU/PER HR
 RATING.
 3.R/A AIR DUCTS ARE NOT SIZED.
 4. MAIN SUPPLY AIR DUCTS NOT SIZED.
 5. PROVIDE FOR R/A OUT OF BEDROOM,
 OFFICE/GBRM. 2001 FBC/M 601.4 BALANCED
 RETURN AIR.
  
 PAT RAFTER 561/805/6728 .
 PLEASE CALL IF THEAR ENY QUESTIONS.