| 2005-02-10 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | I SPOKE WITH THE OWNER/CONTRACTOR WHO | | | INDICATED HE WANTS TO INSTALL AN | | | UPGRADED SERVICE. PLEASE PROVIDE THE | | | FOLLOWING FOR REVIEW. | | | | | | 1} A RISER DIAGRAM FOR ALL ELECTRICAL | | | EQUIPMENT. | | | | | | 2} PROPSED LOCATIONN OF ALL EQUIPMENT ON | | | THE DRAWING. | | | | | | 3} PLEASE INCLUDE THE AIC RATINGS PER | | | 110.9. CONTACT FPL FOR FAULT CURRENT AT | | | THEIR TRANSFORMER SERVING THE | | | RESIDENCE. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|