2005-02-22 00:00:00PERMIT #05011482
  
 ****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 1.) A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.) ENERGY CALCS REQUIRED, FBC13-101.2.
  
 4.) PROVIDE A COPY OF A SURVEY FOR THIS
 PROPERTY.
  
 5.) THE ARCHITECT'S SEAL IS TO BE DATED,
 FAC61G1-16.003.
  
 6.) EMERGENCY EGRESS REQUIRED, FBC
 1005.4.SHOW WINDOW SIZE AND TYPE FOR
 OFFICE/GUEST BEDROOM.
  
 7.) THE ROOF SHEATHING NAILING NOTE
 (SHEET SP) CONFLICTS WITH 2-A4 AND IS
 NOT COMPLIANT FOR ZONE 4, FBC*TABLE
 2306.1.
  
 8.) THE INFORMATION PROVIDED IN ENERGY
 CALC REQUIREMENTS, SHEET SP, CONFLICTS
 WITH THE DETAILS ON THE PLAN.ALSO NOTE
 THAT IF A FORM 600C IS USED FOR ENERGY
 CALCS, THE INSULATION SPECIFIED DOES NOT
 MEET THE MINIMUM PRESCRIPTIVE
 REQUIREMENTS.
  
 9.) SAFETY GLASS REQUIRED IN M.BATH
 (A1), FBC2405.1.PLEASE NOTE ON THE
 PLAN.IMPACT GLASS IS COMPLIANT.
  
 10.) THE SHUTTER PRODUCT APPROVALS
 SUBMITTED ARE NOT NECESSARY AS ALL
 PRODUCTS ARE IMPACT, AND IMPACT WAS
 SPECIFIED ON THE PLAN.IF YOU WOULD
 LIKE TO INSTALL THE SHUTTERS OVER THE
 IMPACT RESISTANT PRODUCTS, PROVIDE A
 SHUTTER ANCHORING SCHEDULE, SEE
 ATTACHED.
  
 11.) THE SOFFIT VENTS ARE TO COMPLY WITH
 FBC2309.7.
  
 12.) INDICATE THE DISTANCE FROM GRADE TO
 THE BOTTOM OF THE FLOOR JOISTS,
 FBC2304.3.
  
 13.) SHOW CRAWL SPACE VENTILATION,
 FBC1804.6.3.1.
  
 14.) 1-A5, STATES "TOP OF FTG ELEVATION
 IS A MINIMUM OF 8? BELOW ADJACENT
 GRADE."DO YOU MEAN BOTTOM OF FOOTING?
 THE BOTTOM IS REQUIRED TO BE MINIMUM OF
 12" BELOW GRADE, FBC1804.1.3.PLEASE
 CLARIFY.
  
 15.) FOOTING B, S1, SHOWS A 12" FOOTER
 DEPTH ALTHOUGH THE NOTE (AND OTHER
 DETAILS) INDICATE 18".BOTTOM OF
 FOUNDATION TO BE A MINIMUM OF 12" BELOW
 GRADE, FBC1804.1.3.THE TOP OF SLAB IS
 TO BE 4" ABOVE GRADE, FBC*1804.1.7.
  
 16.) FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED IN ADDITION TO TEST
 REPORTS, FAC9B72.
 WWW.FLORIDABUILDING.ORG.PLEASE PRINT
 THE STATE PRODUCT APPROVAL, IF
 AVAILABLE, AND CLEARLY INDICATE ON THAT
 APPROVAL WHICH PRODUCT YOU ARE USING.
  
 17.) SPECIFY A DESIGN PRESSURE FOR THE
 ROOF.
  
 18.) PRODUCT APPROVAL REQUIRED FOR THE
 CUSTOM GARAGE DOOR.SEE
 WWW.FLORIDABUILDING.ORG, FAC9B72.
  