| 2005-02-22 00:00:00 | PERMIT #05011482 |
| | |
| | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2001 |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| | TO THE FBC2001 |
| | |
| | 1.) A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2.) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION. |
| | |
| | 3.) ENERGY CALCS REQUIRED, FBC13-101.2. |
| | |
| | 4.) PROVIDE A COPY OF A SURVEY FOR THIS |
| | PROPERTY. |
| | |
| | 5.) THE ARCHITECT'S SEAL IS TO BE DATED, |
| | FAC61G1-16.003. |
| | |
| | 6.) EMERGENCY EGRESS REQUIRED, FBC |
| | 1005.4.SHOW WINDOW SIZE AND TYPE FOR |
| | OFFICE/GUEST BEDROOM. |
| | |
| | 7.) THE ROOF SHEATHING NAILING NOTE |
| | (SHEET SP) CONFLICTS WITH 2-A4 AND IS |
| | NOT COMPLIANT FOR ZONE 4, FBC*TABLE |
| | 2306.1. |
| | |
| | 8.) THE INFORMATION PROVIDED IN ENERGY |
| | CALC REQUIREMENTS, SHEET SP, CONFLICTS |
| | WITH THE DETAILS ON THE PLAN.ALSO NOTE |
| | THAT IF A FORM 600C IS USED FOR ENERGY |
| | CALCS, THE INSULATION SPECIFIED DOES NOT |
| | MEET THE MINIMUM PRESCRIPTIVE |
| | REQUIREMENTS. |
| | |
| | 9.) SAFETY GLASS REQUIRED IN M.BATH |
| | (A1), FBC2405.1.PLEASE NOTE ON THE |
| | PLAN.IMPACT GLASS IS COMPLIANT. |
| | |
| | 10.) THE SHUTTER PRODUCT APPROVALS |
| | SUBMITTED ARE NOT NECESSARY AS ALL |
| | PRODUCTS ARE IMPACT, AND IMPACT WAS |
| | SPECIFIED ON THE PLAN.IF YOU WOULD |
| | LIKE TO INSTALL THE SHUTTERS OVER THE |
| | IMPACT RESISTANT PRODUCTS, PROVIDE A |
| | SHUTTER ANCHORING SCHEDULE, SEE |
| | ATTACHED. |
| | |
| | 11.) THE SOFFIT VENTS ARE TO COMPLY WITH |
| | FBC2309.7. |
| | |
| | 12.) INDICATE THE DISTANCE FROM GRADE TO |
| | THE BOTTOM OF THE FLOOR JOISTS, |
| | FBC2304.3. |
| | |
| | 13.) SHOW CRAWL SPACE VENTILATION, |
| | FBC1804.6.3.1. |
| | |
| | 14.) 1-A5, STATES "TOP OF FTG ELEVATION |
| | IS A MINIMUM OF 8? BELOW ADJACENT |
| | GRADE."DO YOU MEAN BOTTOM OF FOOTING? |
| | THE BOTTOM IS REQUIRED TO BE MINIMUM OF |
| | 12" BELOW GRADE, FBC1804.1.3.PLEASE |
| | CLARIFY. |
| | |
| | 15.) FOOTING B, S1, SHOWS A 12" FOOTER |
| | DEPTH ALTHOUGH THE NOTE (AND OTHER |
| | DETAILS) INDICATE 18".BOTTOM OF |
| | FOUNDATION TO BE A MINIMUM OF 12" BELOW |
| | GRADE, FBC1804.1.3.THE TOP OF SLAB IS |
| | TO BE 4" ABOVE GRADE, FBC*1804.1.7. |
| | |
| | 16.) FLORIDA STATE OR LOCAL PRODUCT |
| | APPROVAL REQUIRED IN ADDITION TO TEST |
| | REPORTS, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG.PLEASE PRINT |
| | THE STATE PRODUCT APPROVAL, IF |
| | AVAILABLE, AND CLEARLY INDICATE ON THAT |
| | APPROVAL WHICH PRODUCT YOU ARE USING. |
| | |
| | 17.) SPECIFY A DESIGN PRESSURE FOR THE |
| | ROOF. |
| | |
| | 18.) PRODUCT APPROVAL REQUIRED FOR THE |
| | CUSTOM GARAGE DOOR.SEE |
| | WWW.FLORIDABUILDING.ORG, FAC9B72. |
| | |