 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE AIC CALCULATIONS PER 110.9.
 THIS IS THE THIRD REQUEST FOR SAME. CALL
 WITH QUESTIONS.
  
 2} INDICATE LOCATION OF SERVICE
 EQUIPMENT. THIS INCLUDES PANELS.
  
 3} THE DRYER CALC MUST COMPLY WITH
 220.18.
  
 4} PLEASE SEE ARTICLE 905.2.2 FBC FOR
 LOCATION, AND TYPE PERMITTED PER
 LOCATION, OF SMOKE DETECTORS. ALSO
 ARTICLE 8-1.4.2 NFPA-72.STAIRWELL AND
 KITCHEN ISSUES.
  
 5} NOTE #13 REGARDING GFI'S SHOULD BE
 REWORDED TO SHOW COMPLIANCE WITH 680.22,
 POOL RECEPTACLES, AND 210.8(A)(6),
 KITCHEN COUNTERTOP RECEPTACLES, OR BE
 REMOVED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  