| Notes |
| Date |
Text |
| 2005-06-02 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE AIC CALCULATIONS PER 110.9. | | | THIS IS THE THIRD REQUEST FOR SAME. CALL | | | WITH QUESTIONS. | | | | | | 2} INDICATE LOCATION OF SERVICE | | | EQUIPMENT. THIS INCLUDES PANELS. | | | | | | 3} THE DRYER CALC MUST COMPLY WITH | | | 220.18. | | | | | | 4} PLEASE SEE ARTICLE 905.2.2 FBC FOR | | | LOCATION, AND TYPE PERMITTED PER | | | LOCATION, OF SMOKE DETECTORS. ALSO | | | ARTICLE 8-1.4.2 NFPA-72.STAIRWELL AND | | | KITCHEN ISSUES. | | | | | | 5} NOTE #13 REGARDING GFI'S SHOULD BE | | | REWORDED TO SHOW COMPLIANCE WITH 680.22, | | | POOL RECEPTACLES, AND 210.8(A)(6), | | | KITCHEN COUNTERTOP RECEPTACLES, OR BE | | | REMOVED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|