Plan Review Notes
Plan Review Notes For Permit 05011469
Permit Number 05011469
Review Stop P
Sequence Number 2
Notes
Date Text
2005-04-14 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SHT A-5 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A) NO TRAP FOR THE WATER CLOSET AS IT
 HAS AN INTEGRAL TRAP. SECTION 1002.1
 B) SHOW THE TRAP AND STANDPIPE ON THE
 WASH MACHINE SECTIONS 901.2.1 & 1002.1.
 C) WASH MACHINE SHALL NOT DISCHARGE
 INTO THE WET-VENTED BATHROOM GROUP.
 SECTION 909.1
 D) LAV ON SEPARATE WALL FROM W/M
 SECTION 104.2.1.
 E) 2ND FLOOR BATHROOMS DO NOT REFLECT
 THE FLOOR PLAN. SECTION 104.2.1.
 2) SEE ATTACHED SHEET SHOWING AN EXAMPLE
 OF A SANT. RISER DIAGRAM THAT MEETS THE
 CODE REQUIREMENTS AND REFLECTS THE FLOOR
 PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]