| 2005-04-01 00:00:00 | ********** UNSAT 2ND REVIEW *********** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW DONE BY BILL TROBAUGH STILL NEED |
| | TO BE ADDRESSED. |
| | |
| | PLEASE ALSO SEE "NEW NOTES AT BOTTOM OF |
| | PLANS. |
| | |
| | 1)NOTE: NOTE #1, YES, THE RISER DIAGRAM |
| | NOW HAS CONDUIT AND CONDUCTOR SIZES, |
| | HOWEVER PLEASE SEE SEC'S ARE TOO SMALL |
| | FOR 400A SERVICE PROVIDED. |
| | PLEASE SEE MIN SEC'S TO BE PER 310.16, |
| | PER 240.4 |
| | PLEASE ALSO SHOW CONDUCTORS FROM GUTTER |
| | TO MAINS. |
| | |
| | 2)NOTE: NOTE #2, NO, PLEASE SEE 250.66 |
| | FOR MIN SIZE FOR GROUNDING ELECTRODE |
| | CONDUCTOR. PLEASE SEE MIN 1/0. |
| | |
| | 3)NOTE: NOTE #3,NO, PLEASE SUBMIT PER |
| | PREVIOUS NOTES. 110.9 |
| | |
| | 4)NOTE: NOTE #4 OK. |
| | |
| | 5)NOTE: NOTE #5 OK. |
| | |
| | 6)NOTE: NOTE #6 NO, PLEASE SEE NOTE #13. |
| | PLEASE ALSO SEE NEW NOTES. |
| | |
| | 7)NOTE: NOTE #7 OK |
| | |
| | 8)NOTE: NOTE #8 OK. |
| | PLEASE ALSO SEE NEW NOTES AT BOTTOM. |
| | |
| | 9)NOTE: NOTE #9 OK. |
| | |
| | 10)NOTE: NOTE #10 OK. |
| | |
| | 11)NOTE: NOTE #11 NO, PLEASE SEE |
| | PREVIOUS COMNMENTS, PLEASE SEE 220.18 |
| | MIN VA REQUIRED. |
| | PLEASE ALSO SEE PANEL SCHEDULES DO NOT |
| | INDICATE DRYER(S) AT ALL?? |
| | |
| | 12)NOTE: NOTE #12 OK. |
| | |
| | 13)NOTE: NOTE #13 OK. |
| | |
| | 14)NOTE: NOTE #14 OK. |
| | |
| | 15)NOTE: NOTE #15 NO, PLEASE SEE RECEPTS |
| | ADDED , HOWEVER STILL DO NOT INDICATE |
| | GFI'S. |
| | |
| | 16)NOTE: NOTE #15, NO, PLEASE SEE |
| | 210.8A6, THIS WAS IN SECOND PART OF |
| | NOTE. PLEASE SEE SYMBOL SCHEDULE, PLEASE |
| | ADJUST SYMBOLS TO CORRELATE WITH PLANS |
| | AND SEPARATE SYMBOLS FOR GFI /HALF |
| | SWICTHED RECEPTS. |
| | |
| | 17)NOTE: NOTE #17 OK. |
| | |
| | 18)NOTE: NOTE #18, NO, PLEASE SEE |
| | PREVIOUS NOTE. |
| | |
| | ** NEW NOTES** |
| | |
| | 1)NOTE: PLEASE SEE GFI NOTE/ NOTE #13, |
| | MENTIONS ALL INDICATED RECEPTS TO BE |
| | WP(WEATHER PROOF)? |
| | PLEASE SEE MENTIONS RECETPS WITHIN 15' |
| | OF POOL? PLEASE SEE CODE REQUIRES |
| | WITH-IN 20', |
| | PLEASE SEE REQUIREMENTS FOR RECEPTS |
| | WITH-IN 6'/4' OF SINK CHANGED IN THE 93 |
| | NEC. |
| | PLEASE SEE 2002 NEC 210.8 |
| | |
| | 2)NOTE: PLEASE SEE THERE ARE MANY ITEMS |
| | LISTED ON PANEL SCHEDULES WHICH DO NOT |
| | INDICATE OCP, AWG ETC. |
| | |
| | 3)NOTE: PLEASE SEE PANEL SCHEDULE |
| | INDICATES TWO WATER HEATERS? |
| | |
| | 4)NOTE: PLEASE SEE PLANS INDICATE "SPA |
| | TUB", DOES THIS CONTAIN ELEC MOTOR? IF |
| | SO , PLEASE INDICATE GFI PROTECTION PER |
| | 680.71 |
| | |
| | 5)NOTE: PLEASE SEE NUMEROUS DEVICE |
| | REQUIRED TO BE SHOWN AS GFI PER 210.8 |
| | |
| | 6)NOTE: PLEASE SEE COPY OF FS |
| | 553.80(2)(B) ATTACHED WITH RESPECT TO |
| | DESIGN PROFESSIONAL. |
| | IF PLANS COME BACK WITH ANY OF THE SAME |
| | COMMENTS FROM THE FIRST TWO REVIEWS NOT |
| | ADDRESSED, A 4X FEE SHALL BE ACCESSED |
| | FOR THE PLAN REVIEW PORTION OF THE |
| | PREMIT FEE.(30%) |
| | |
| | |
| | PLEASE SE SURE TO REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |