Plan Review Notes
Plan Review Notes For Permit 05011469
Permit Number 05011469
Review Stop E
Sequence Number 2
Notes
Date Text
2005-04-01 00:00:00********** UNSAT 2ND REVIEW ***********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW DONE BY BILL TROBAUGH STILL NEED
 TO BE ADDRESSED.
  
 PLEASE ALSO SEE "NEW NOTES AT BOTTOM OF
 PLANS.
  
 1)NOTE: NOTE #1, YES, THE RISER DIAGRAM
 NOW HAS CONDUIT AND CONDUCTOR SIZES,
 HOWEVER PLEASE SEE SEC'S ARE TOO SMALL
 FOR 400A SERVICE PROVIDED.
 PLEASE SEE MIN SEC'S TO BE PER 310.16,
 PER 240.4
 PLEASE ALSO SHOW CONDUCTORS FROM GUTTER
 TO MAINS.
  
 2)NOTE: NOTE #2, NO, PLEASE SEE 250.66
 FOR MIN SIZE FOR GROUNDING ELECTRODE
 CONDUCTOR. PLEASE SEE MIN 1/0.
  
 3)NOTE: NOTE #3,NO, PLEASE SUBMIT PER
 PREVIOUS NOTES. 110.9
  
 4)NOTE: NOTE #4 OK.
  
 5)NOTE: NOTE #5 OK.
  
 6)NOTE: NOTE #6 NO, PLEASE SEE NOTE #13.
 PLEASE ALSO SEE NEW NOTES.
  
 7)NOTE: NOTE #7 OK
  
 8)NOTE: NOTE #8 OK.
 PLEASE ALSO SEE NEW NOTES AT BOTTOM.
  
 9)NOTE: NOTE #9 OK.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 NO, PLEASE SEE
 PREVIOUS COMNMENTS, PLEASE SEE 220.18
 MIN VA REQUIRED.
 PLEASE ALSO SEE PANEL SCHEDULES DO NOT
 INDICATE DRYER(S) AT ALL??
  
 12)NOTE: NOTE #12 OK.
  
 13)NOTE: NOTE #13 OK.
  
 14)NOTE: NOTE #14 OK.
  
 15)NOTE: NOTE #15 NO, PLEASE SEE RECEPTS
 ADDED , HOWEVER STILL DO NOT INDICATE
 GFI'S.
  
 16)NOTE: NOTE #15, NO, PLEASE SEE
 210.8A6, THIS WAS IN SECOND PART OF
 NOTE. PLEASE SEE SYMBOL SCHEDULE, PLEASE
 ADJUST SYMBOLS TO CORRELATE WITH PLANS
 AND SEPARATE SYMBOLS FOR GFI /HALF
 SWICTHED RECEPTS.
  
 17)NOTE: NOTE #17 OK.
  
 18)NOTE: NOTE #18, NO, PLEASE SEE
 PREVIOUS NOTE.
  
 ** NEW NOTES**
  
 1)NOTE: PLEASE SEE GFI NOTE/ NOTE #13,
 MENTIONS ALL INDICATED RECEPTS TO BE
 WP(WEATHER PROOF)?
 PLEASE SEE MENTIONS RECETPS WITHIN 15'
 OF POOL? PLEASE SEE CODE REQUIRES
 WITH-IN 20',
 PLEASE SEE REQUIREMENTS FOR RECEPTS
 WITH-IN 6'/4' OF SINK CHANGED IN THE 93
 NEC.
 PLEASE SEE 2002 NEC 210.8
  
 2)NOTE: PLEASE SEE THERE ARE MANY ITEMS
 LISTED ON PANEL SCHEDULES WHICH DO NOT
 INDICATE OCP, AWG ETC.
  
 3)NOTE: PLEASE SEE PANEL SCHEDULE
 INDICATES TWO WATER HEATERS?
  
 4)NOTE: PLEASE SEE PLANS INDICATE "SPA
 TUB", DOES THIS CONTAIN ELEC MOTOR? IF
 SO , PLEASE INDICATE GFI PROTECTION PER
 680.71
  
 5)NOTE: PLEASE SEE NUMEROUS DEVICE
 REQUIRED TO BE SHOWN AS GFI PER 210.8
  
 6)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED WITH RESPECT TO
 DESIGN PROFESSIONAL.
 IF PLANS COME BACK WITH ANY OF THE SAME
 COMMENTS FROM THE FIRST TWO REVIEWS NOT
 ADDRESSED, A 4X FEE SHALL BE ACCESSED
 FOR THE PLAN REVIEW PORTION OF THE
 PREMIT FEE.(30%)
  
  
 PLEASE SE SURE TO REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  