Plan Review Notes For Permit 05011469
Permit Number 05011469
Review Stop P
Sequence Number 1
Notes
Date Text
2005-02-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) SHT A-5 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS.
 A) KITCHEN SINK IS NOT SHOWN ON RISER.
 SECTION 104.2.1.
 B) A TRAP IS REQUIRED FOR THE WASH
 MACHINE. SECTION 1002.1.
 C) A STANDPIPE IS REQUIRED FOR THE WASH
 MACHINE. SECTION 1002.1.
 D) A CLEANOUT IS REQUIRED, 4' ABOVE THE
 FLOOR AT THE WASH MACHINE STACK. SECTION
 708.10.
 E) WASH MACHINE AND W/C FOR POWDER ROOM
 ARE ON A COMMON WALL. THE SANT. RISER
 INDICATES THAT THE FIXTURES ARE ON
 DIFFERENT WALLS. RISER SHALL REFLECT THE
 FLOOR PLAN.
 F) BATH #2 SHALL BE SHOWN AS DIRECTLY
 ABOVE THE POWDER ROOM ON THE FIRST FLOOR
 ON THE FLOOR PLAN, BUT IS SHOWN ON THE
 OTHER END OF THE HOUSE ON THE RISER.
 SECTION 104.2.1.
 G) CLEANOUT LINE UPSTREAM OF BATH #2 IS
 PIPED TO WHAT LOCATION? PLEASE CLARIFY.
 SECTION 104.2.1.
 H) MASTER BATH SHOWS A SHOWER, THEN A
 W/C, THEN A TUB, THEN A LAV. FLOOR PLAN
 SHOWS A TUR, A W/C THEN A LAV. PLEASE
 HAVE SANT. RISER DIAGRAM REFLECT THE
 FLOOR PLAN AND SHOW HOW THE PIPING WILL
 BE INSTALLED. SECTION 104.2.1.
  