| Plan Review Notes For Permit 05011469 |
| Permit Number |
05011469 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | | | | 1) SHT A-5 SANITARY RISER DIAGRAM DOES | | | NOT REFLECT THE FLOOR PLAN, NOR DOES IT | | | MEET CODE REQUIREMENTS. | | | A) KITCHEN SINK IS NOT SHOWN ON RISER. | | | SECTION 104.2.1. | | | B) A TRAP IS REQUIRED FOR THE WASH | | | MACHINE. SECTION 1002.1. | | | C) A STANDPIPE IS REQUIRED FOR THE WASH | | | MACHINE. SECTION 1002.1. | | | D) A CLEANOUT IS REQUIRED, 4' ABOVE THE | | | FLOOR AT THE WASH MACHINE STACK. SECTION | | | 708.10. | | | E) WASH MACHINE AND W/C FOR POWDER ROOM | | | ARE ON A COMMON WALL. THE SANT. RISER | | | INDICATES THAT THE FIXTURES ARE ON | | | DIFFERENT WALLS. RISER SHALL REFLECT THE | | | FLOOR PLAN. | | | F) BATH #2 SHALL BE SHOWN AS DIRECTLY | | | ABOVE THE POWDER ROOM ON THE FIRST FLOOR | | | ON THE FLOOR PLAN, BUT IS SHOWN ON THE | | | OTHER END OF THE HOUSE ON THE RISER. | | | SECTION 104.2.1. | | | G) CLEANOUT LINE UPSTREAM OF BATH #2 IS | | | PIPED TO WHAT LOCATION? PLEASE CLARIFY. | | | SECTION 104.2.1. | | | H) MASTER BATH SHOWS A SHOWER, THEN A | | | W/C, THEN A TUB, THEN A LAV. FLOOR PLAN | | | SHOWS A TUR, A W/C THEN A LAV. PLEASE | | | HAVE SANT. RISER DIAGRAM REFLECT THE | | | FLOOR PLAN AND SHOW HOW THE PIPING WILL | | | BE INSTALLED. SECTION 104.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|