| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} SHOW CONDUIT AND CONDUCTOR SIZES FOR |
| | THE SERVICE RISER EQUIPMENT, QUOTED CODE |
| | ARTICLES ARE UNACCEPTABLE PER 104.2.1 |
| | FBC. |
| | |
| | 2} SHOW GROUNDING PER 250 ON THE RISER. |
| | |
| | 3} GIVE AIC CALCULATIONS AND RATINGS FOR |
| | EQUIPMENT PER 110.9. |
| | |
| | 4} SHOW LOCATION OF ALL SERVICE |
| | EQUIPMENT ON THE PLANS. PLEASE SEE |
| | 230.70 CWPB FOR DISCONNECT |
| | REQUIREMENTS. |
| | |
| | 5} LOCATE THE CONDENSING UNIT ON THE |
| | PLAN FOR COMPLIANCE OF 210.63 AND |
| | 440.14. |
| | |
| | 6} REFERRING TO NOTE #13 IN THE |
| | ELECTRICAL NOTES, PLEASE ALSO SEE |
| | 210.8(A)(6) RE:KITCHEN RECEPTACLES. |
| | |
| | 7} THE OCP FOR 15KW OF HEAT IS INCORRECT |
| | ON THE PANEL SCHEDULE. PLEASE CORRELATE |
| | WITH MECHANICAL CONTRACTOR. THIS AHU IS |
| | EXCEPTIONALLY LARGE FOR THE THE |
| | RESIDENCE SIZE.SAME COMMENT FOR "A/C |
| | COMPRESSOR UNIT" |
| | |
| | 8} WATER HEATER HAS #8 CONDUCTORS FED |
| | FROM A 20 AMP BREAKER. PLEASE CORRECT. |
| | |
| | 9} THE DISHWASHER HAS #10 CONDUCTORS ON |
| | A 20 AMP BREAKER, ALTHOUGH NOT A |
| | VIOLATION, THE INSTALLATION MUST BE AS |
| | REVIEWED PLANS. |
| | |
| | 10} CIRCUITS 14-19 LABLED "GENERAL |
| | LIGHTING" #14 CONDUCTORS ON A 20 AMP OCP |
| | ARE IN VIOLATION OF 310.16. |
| | |
| | 11} THE DRYER CALCULATION MUST COMPLY |
| | WITH 220.18 FOR THE CALCULATION |
| | (5KW.)SHOWN TWICE IN THE SAME CALC, ONCE |
| | @ 4500, P[LEASE CORRELATE. |
| | |
| | 12} NOTE #2 IN THE "GENERAL ELECTRICAL |
| | NOTES" REFERS TO TW WIRE. PLEASE NOTE |
| | THAT THE 60O TABLE MUST BE USED FOR |
| | THESE CONDUCTORS IF THIS NOTE REMAINS ON |
| | THE PLAN. |
| | |
| | 13} THE LAUNDRY CIRCUIT MUST COMPLY WITH |
| | 220.16(B)(1500W). |
| | |
| | 14} THERE IS NO LOW VOLTAGE SYSTEMS |
| | SHOWN ON THE PLAN. IF THESE SYSTEMS ARE |
| | ADDED AT A LATTER DATE THEY WILL REQUIRE |
| | SEPERATE PLANS, REVIEWS AND |
| | APPLICATIONS. |
| | |
| | 15} PLEASE ADD AND SHOW LOCATIONS OK |
| | REQUIRED OUTSIDE RECEPTACLES PER |
| | 210.52(E) & 210.8(A)(3). |
| | |
| | 16) CHECK KITCHEN COUNTERTOP RECEPTACLE |
| | SPACING PER 210.52(C)(1). ALSO SEE |
| | 210.8(A)(6). |
| | |
| | 17} PLACE A SMOKE DETECTOR AT THE |
| | STAIRWELL ON THE 2ND FLOOR PER 905.2.2 |
| | FBC. |
| | |
| | 18} THE DESIGNER OF RECORD MUST TAKE |
| | RESPONSIBILITY FOR THE DRAWINGS PER |
| | 104.2.1 FBC AND 61G15.23.002 FAC. |
| | |
| | |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |