Plan Review Notes
Plan Review Notes For Permit 05011469
Permit Number 05011469
Review Stop E
Sequence Number 1
Notes
Date Text
2005-02-03 00:00:00 
  
  
  
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW CONDUIT AND CONDUCTOR SIZES FOR
 THE SERVICE RISER EQUIPMENT, QUOTED CODE
 ARTICLES ARE UNACCEPTABLE PER 104.2.1
 FBC.
  
 2} SHOW GROUNDING PER 250 ON THE RISER.
  
 3} GIVE AIC CALCULATIONS AND RATINGS FOR
 EQUIPMENT PER 110.9.
  
 4} SHOW LOCATION OF ALL SERVICE
 EQUIPMENT ON THE PLANS. PLEASE SEE
 230.70 CWPB FOR DISCONNECT
 REQUIREMENTS.
  
 5} LOCATE THE CONDENSING UNIT ON THE
 PLAN FOR COMPLIANCE OF 210.63 AND
 440.14.
  
 6} REFERRING TO NOTE #13 IN THE
 ELECTRICAL NOTES, PLEASE ALSO SEE
 210.8(A)(6) RE:KITCHEN RECEPTACLES.
  
 7} THE OCP FOR 15KW OF HEAT IS INCORRECT
 ON THE PANEL SCHEDULE. PLEASE CORRELATE
 WITH MECHANICAL CONTRACTOR. THIS AHU IS
 EXCEPTIONALLY LARGE FOR THE THE
 RESIDENCE SIZE.SAME COMMENT FOR "A/C
 COMPRESSOR UNIT"
  
 8} WATER HEATER HAS #8 CONDUCTORS FED
 FROM A 20 AMP BREAKER. PLEASE CORRECT.
  
 9} THE DISHWASHER HAS #10 CONDUCTORS ON
 A 20 AMP BREAKER, ALTHOUGH NOT A
 VIOLATION, THE INSTALLATION MUST BE AS
 REVIEWED PLANS.
  
 10} CIRCUITS 14-19 LABLED "GENERAL
 LIGHTING" #14 CONDUCTORS ON A 20 AMP OCP
 ARE IN VIOLATION OF 310.16.
  
 11} THE DRYER CALCULATION MUST COMPLY
 WITH 220.18 FOR THE CALCULATION
 (5KW.)SHOWN TWICE IN THE SAME CALC, ONCE
 @ 4500, P[LEASE CORRELATE.
  
 12} NOTE #2 IN THE "GENERAL ELECTRICAL
 NOTES" REFERS TO TW WIRE. PLEASE NOTE
 THAT THE 60O TABLE MUST BE USED FOR
 THESE CONDUCTORS IF THIS NOTE REMAINS ON
 THE PLAN.
  
 13} THE LAUNDRY CIRCUIT MUST COMPLY WITH
 220.16(B)(1500W).
  
 14} THERE IS NO LOW VOLTAGE SYSTEMS
 SHOWN ON THE PLAN. IF THESE SYSTEMS ARE
 ADDED AT A LATTER DATE THEY WILL REQUIRE
 SEPERATE PLANS, REVIEWS AND
 APPLICATIONS.
  
 15} PLEASE ADD AND SHOW LOCATIONS OK
 REQUIRED OUTSIDE RECEPTACLES PER
 210.52(E) & 210.8(A)(3).
  
 16) CHECK KITCHEN COUNTERTOP RECEPTACLE
 SPACING PER 210.52(C)(1). ALSO SEE
 210.8(A)(6).
  
 17} PLACE A SMOKE DETECTOR AT THE
 STAIRWELL ON THE 2ND FLOOR PER 905.2.2
 FBC.
  
 18} THE DESIGNER OF RECORD MUST TAKE
 RESPONSIBILITY FOR THE DRAWINGS PER
 104.2.1 FBC AND 61G15.23.002 FAC.
  
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026