2005-03-01 00:00:00PROVISO:
 PLEASE NOTE, TERMINATION OF GREASE
 EXHAUST DUCT SHALL BE A MINIMUM OF 2 FT
 HORIZONTAL DISTANCE BETWEEN VERTICAL
 DISCHARGE FANS & PARAPETS PROVIDED THAT
 THE PARAPET IS NOT HIGHER THAN THE TOP
 OF THE FAN DISCHARGE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  