| Plan Review Notes For Permit 05011466 |
| Permit Number |
05011466 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2005-02-01 00:00:00 | DENIED: | | | 1.PLEASE INDICATE DISTANCE FROM | | | PROPERTY LINES, ADJACENT OR CONTIGUOUS | | | BUILDINGS, AND FRESH AIR INTAKES IN | | | ACCORDANCE WITH 2001 FBC(M)506.3.14.3. | | | | | | 2.PROVIDE CLEARANCE TO COMBUSTIBLES | | | PER 2001 FBC(M)506.3.8. | | | | | | 3.PLAN SHEET 2 OF 2 GENERAL NOTES, #1 | | | INDICATES HOOD CONSTRUCTED WITH 18GA | | | STAINLESS.NOTE #2 INDICATES GREASE | | | DUCT 16GA STAINLESS.DISSIMILAR METALS, | | | PLEASE CLARIFY. | | | | | | 4.PLEASE NOTE PER 2001 FBC(M) 506.3.6, | | | AIR VELOCITY WITHIN THE DUCT SYSTEM | | | SHALL NOT BE LESS THAN 1,500 FPM BUT NOT | | | GREATER THAN 2,500 FPM. | | | | | | ADDITIONAL PERMIT REQUIRED FOR THE FIRE | | | SUPPRESSION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT(561)805-6719. |
|