Plan Review Notes
Plan Review Notes For Permit 05011466
Permit Number 05011466
Review Stop M
Sequence Number 1
Notes
Date Text
2005-02-01 00:00:00DENIED:
 1.PLEASE INDICATE DISTANCE FROM
 PROPERTY LINES, ADJACENT OR CONTIGUOUS
 BUILDINGS, AND FRESH AIR INTAKES IN
 ACCORDANCE WITH 2001 FBC(M)506.3.14.3.
  
 2.PROVIDE CLEARANCE TO COMBUSTIBLES
 PER 2001 FBC(M)506.3.8.
  
 3.PLAN SHEET 2 OF 2 GENERAL NOTES, #1
 INDICATES HOOD CONSTRUCTED WITH 18GA
 STAINLESS.NOTE #2 INDICATES GREASE
 DUCT 16GA STAINLESS.DISSIMILAR METALS,
 PLEASE CLARIFY.
  
 4.PLEASE NOTE PER 2001 FBC(M) 506.3.6,
 AIR VELOCITY WITHIN THE DUCT SYSTEM
 SHALL NOT BE LESS THAN 1,500 FPM BUT NOT
 GREATER THAN 2,500 FPM.
  
 ADDITIONAL PERMIT REQUIRED FOR THE FIRE
 SUPPRESSION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT(561)805-6719.