2005-06-16 00:00:00PROVISO:
 JP UNIT IS A "COMBINED" UNIT WHICH
 CHANGES THE AGGREGATE AIR TO EXCEED
 2,000 CFM.DUCT SMOKE DETECTORS WITH
 NOTIFICATION WILL BE REQUIRED IN
 ACCORDANCE WITH 2001 FBC(M)606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.